Connecting The Sensor Hub; Module Variants; Sensor/Actuator Interface; Extension Port - Balluff BNI IOL-302-002-Z046 User Manual

Io-link 1.1 sensor/actuator hub with extension port
Hide thumbs Also See for BNI IOL-302-002-Z046:
Table of Contents

Advertisement

Balluff Network Interface / IO-Link BNI IOL-302-002-Z046
3
First Steps
Connecting the
sensor hub

Module variants

Sensor/actuator
interface

Extension port

www.balluff.com
 Connect ground conductor to the functional ground connection, if available.
 Connect the incoming IO-Link cable to the sensor hub.
Note
A standardized sensor cable is used to connect to the higher-level to the
IO-Link master module. Maximum length of 20 m.
Sensor hub variants
BNI IOL-302-002-Z046
Standard in-/output M8
Pin
1
4
3
Note
For the digital inputs, the input guideline specified in EN 61131-2, Type 3 applies
Note
Unused input port sockets must be fitted with blind caps to ensure the IP67 degree
of protection.
Extension port (M8, female)
The port acts like a sensor/actuator interface if the extension function is disabled.
Pin
1
4
3
Note
A standardized sensor cable is used to connect to the device/sensor to be
expanded. Maximum length of 20 m.
Function
IN / OUT
+24V
Input / Output
0V
Function
IN / OUT
+24V
Communication
0V
Digital port
IN / OUT
8