Cable Rings And Troughs; Cable Brackets; Cross-Connect System; System Specifications - ADC DSX-3 Installation Manual

Rear cross-connect system
Hide thumbs Also See for DSX-3:
Table of Contents

Advertisement

ADCP-80-353 • Issue 2 • August 2002 • Section 1: Description
4.4

Cable Rings and Troughs

Vertical cable rings at the rear of the bay allow for routing of cross-connect jumpers up and
down each side of the bay. Cable troughs at the top and bottom of the bay provide for the
routing of cross-connect jumpers between bays.
4.5

Cable Brackets

The cables are brought in at the sides of the bay and tied to the cable brackets.
4.6

Cross-Connect System

The cross-connect system bay is an unequal flange type, 213 × 65.88 × 30.48 cm (84 × 25.94 × 12
inches). Shelf mounting holes are spaced at 2.54 cm (1 inch). An AC outlet may be provided at
the bottom front of the bay as an auxiliary source of 110 Vac primary power.

5 SYSTEM SPECIFICATIONS

Specifications for the DSX-3 (DSX-4U-24) Rear Cross-Connect System are shown in
PARAMETER
Physical
Height:
Width:
Depth:
Weight:
Power
Voltage:
Current:
Environmental
Operating Temperature:
Storage Temperature:
Operating and Storage Humidity:
Functional
Characteristic Impedance:
Insertion Loss:
Crosstalk:
Return Loss:
Monitor Level:
Page 1-10
© 2002, ADC Telecommunications, Inc.
Table 1-2. System Specifications
SPECIFICATION
2.13 m (7.0 feet)
55.72 cm (21.94 inches)
30.48 cm (12 inches)
163 kg (360 pounds) (fully equipped)
–48 Vdc
10 mA for each lit LED tracer lamp
–40° to 65° C (–40° to +149° F)
–55° to +85° C (–67° to +185° F)
0% to 95% without condensation
75 ohms unbalanced.
Less than 0.8 dB at 22.368 mHz and less than 1.9 dB at
137.088 mHz with up to 27 feet (8.23 m) of cross-connect cable.
Better than 60 dB.
Greater than 20 dB (DC to 300 mHz).
21.5 dB ±1.5 dB below signal level (DC to 300 mHz).