Wiring Diagram - Trane ComfortLink 4TWZ0060A1000A Manual

Table of Contents

Advertisement

MANuAL CHARGING OR CHARGe ASSIST
COOLing BeTWeeN 55°F ANd 120°F Od AMBIeNT
It is recommended to install manufacturer approved matched indoor and
outdoor systems.
All approved split systems are ARI rated with only TXV indoor systems.
The benefits of installing approved indoor and outdoor split systems are
maxi mum efficiency, optimum performance and the best overall system
reliability. The following charging methods are therefore prescribed for
matched systems with indoor TXVs.
1. Subcooling using the R-410A Refrigerant Charging Chart (in the cooling
mode) is the only recommended method of charging between 55°F and
120°F ambient temperatures.
2. When charging for ambient temperatures above 120°F, charge to 10°
subcooling. It is important to return when outdoor ambient temperature
is between 55°F and 120°F to verify system charge per these instruc-
tions.
3. For best results – the indoor temperature should be kept between 70°F
to 80°F. Add system heat if needed.
4. At startup, or whenever charge is removed or added, the system must
be operated for a minimum twenty (20) minutes to stabilize before
accurate measurements can be made. (Feature of Charge Assist™)
5. Measure Liquid Line Temperature and Refrigerant Pressure at service
valves. (Not required with Charge Assist.™)
6. Determine total refrigerant line length, and height (lift) if indoor section is above the condenser. Set dip switches on Charge Assist™ board as
indicated in the Subcool Charging Corrections Table on page 2 .
7. Locate your liquid line temperature in the left column of the table, and the intersecting liquid line gage pressure under the DIPSWITCH selection
column. Add refrigerant to raise the pressure to match the table, or remove refrigerant to lower the pressure. For manual charging, always wait twen-
ty (20) minutes for the system conditions to stabilize before adjusting charge again. (Not required with Charge Assist.™)
8.
Charge Assist port is designed for liquid refrigerant charging.
9.
When system is correctly charged, you can refer to System Pressure Curves (on page 8) to verify typical performance.

WIRING dIAGRAM

5 TON HP R410A REFRIGERANT CHARGING CHART
MeTHOd IN
TM
Liquid
Temp (°F)
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
dWG. NO. 4TWZ0060-SF-1B
LIQUID GAGE PRESSURE (PSIG)
ONLY DIPSWITCH
ONLY DIPSWITCH
1 ON
2 ON
LOWER *
MIDDLE
208
208
225
225
242
242
260
260
280
280
300
300
322
322
345
345
369
369
394
394
420
420
447
447
476
476
505
505
536
536
* Data is based on 14.8° of subcooling at a 95° ambient
** Data is based on 16.7° of subcooling at a 95° ambient
PRINTED FROM D155859P04 REV 4
ONLY DIPSWITCH
3 ON
UPPER & 4TEE3_10
DOWNFLOW & HORIZ.
LEFT **
210
227
245
264
284
305
327
350
374
400
426
454
483
513
544
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents