Download Print this page
Intermatic FL100HPS Installation Instructions
Intermatic FL100HPS Installation Instructions

Intermatic FL100HPS Installation Instructions

Hid flood light - fl series

Advertisement

Quick Links

HID Flood Light - FL Series
INSTALLATION INSTRUCTIONS
Lamp Types: High Pressure Sodium 100 Watt
Models: FL100HPS
IMPORTANT:
ELECTRICAL REQUIREMENTS
A qualified electrician should complete all required wiring. This fixture will accept 120, 208, 240 or 277
Volts AC and must be properly grounded for safety. A mounting suitable for outdoor use and rated for
wet locations is required. Follow all applicable electrical codes and regulations
WARNING: Electric shock hazard
Disconnect power at circuit breaker or fuse box before installing or servicing light.
WARNING: Fire hazard
USE MIN 60ºC SUPPLY CONDUCTORS.
CONNECT TO SUPPLY IN EXTERNAL JUNCTION BOX ONLY.
Lamp and housing become very hot during use.
Ensure free air circulation around unit to dissipate heat.
Avoid enclosed locations and locations where flammable debris (leaves, cut grass, etc.) might collect.
Avoid locations where humans or animals might accidentally touch fixture.
WARNING: Explosion hazard
Never operate light without securing the lens door. When light is operating, the gas in the lamp inner arc tube
is at high pressure.
Never operate light if the fixture lens or outer glass envelope of the lamp is broken or missing.
WARNING: Explosion hazard
Wear safety glasses and gloves when handling lamp, High Pressure Sodium outer envelope is under vacuum
and could implode.
MOUNTING & WIRING
1. Screw the threaded mounting arm of the fixture into 1/2" NPS mounting hole on mounting device.
Tighten locknut to secure fixture. See Figure 1.
CAUTION: Mount the fixture so lamp is horizontal. (See Figure 2)
Mounting
Arm Bolt
Locknut
FOR OUTDOOR USE ONLY
NOT FOR USE IN HAZARDOUS ATMOSPHERES
Read instruction sheet carefully before installing fixture.
Retain instructions for future reference.
Figure 1
.
Clip
Lens
Cover
Hinge
Figure 2
Install with lamp horizontal

Advertisement

loading

Summary of Contents for Intermatic FL100HPS

  • Page 1 HID Flood Light - FL Series INSTALLATION INSTRUCTIONS Lamp Types: High Pressure Sodium 100 Watt Models: FL100HPS NOT FOR USE IN HAZARDOUS ATMOSPHERES IMPORTANT: ELECTRICAL REQUIREMENTS A qualified electrician should complete all required wiring. This fixture will accept 120, 208, 240 or 277 Volts AC and must be properly grounded for safety.
  • Page 2: Lamp Replacement

    5. Properly dispose of lamp per manufacturer’s recommendations. If within one (1) year from the date of purchase, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, free of charge. This warranty is extended to the original purchaser only and is not transferable.