Low Voltage Inputs

Any EM1400 series relay panel may be used with
"digital" switches that sit on the data bus and are
connected with Cat. 5 cable with RJ45 connectors.
Additionally, one may order the EM1400 with the op-
tional contact closure inputs. These can be used with
contact closure devices - even ordinary wall switches
available from any hardware store.
!
This Product Guide does not contain system-wide
wiring or activation procedures. Please refer to
the System Start-Up Guide for system wiring and
activation details and for hook-up details to other
panels or digital devices.
The photocell input in the
Master LCP allows a pho-
tocell to be included in time
schedules. Up to 8 trigger
points are available for mul-
tiple schedules.

Contact Closure Inputs

14 programmable contact inputs can control any
relay(s) in any panel(s), for manual (on/off) or over-
ride.
Use shielded cable for distances over 150 feet.
Connect the drain wire to the GND input of the panel
only. Do not connect the drain wire to a remote
switch!
!
This system uses a fl oating ground - do not use
earth ground.
Cat. 5 cables for the
digital bus plug in to the
RJ45 sockets at the bot-
tom of the panel.
SCROLL
TAB
UP
UP
EXIT
SCROLL
TAB
DOWN
DOWN
Input
+4.1
This maintained switch is
programmed as "maintain" in
the Button Sub-Menu for up
to 8 relays or as a Maintain
Group for more than 8 relays
(see Basic Programming
Guide).
Occupant sensors with isolat-
ed dry contacts may be used
to control relays or groups.
Set the timer on the occupant
sensor at the desired time
delay and program the input
as "maintain."
isolated
Occ
(auxilliary)
Sensor
contact
Center-Off momentary
switches are two separate
contacts, and use two inputs.
Program one as "momen-
tary on" and the other as
"momentary off."
Relay outputs from any exter-
nal system, such as security,
are usually programmed
EN
"maintained" or as "momen-
tary on" for a timer.
Momentary switches are
often programmed as "tog-
gle" or "momentary on" (for
an override switch). They
can also be "off" or "mixed
mode".
Pg. 5