Troubleshooting; General; Alarms And Fault Conditions - Xantrex PV-100208 Operation And Maintenance Manual

100 kw grid-tied photovoltaic inverter
Table of Contents

Advertisement

SECTION 5

TROUBLESHOOTING

GENERAL

In the event of a fault, the PV-100208 will annunciate the condition at the operator interface. The PV-
100208 will execute an orderly shutdown and remain faulted until the fault is cleared (manually or
automatically).
In general, the operator should respond to any PV-100208 fault as follows:
1. The source of the fault should be sought by referring to the following chart.
2. Rectify the fault condition and attempt to clear the fault by cycling the on/off switch.
3. If the problem cannot be corrected, note and write down the fault code and description, then contact
your Xantrex Technology distributor for assistance or service.
ALARM AND FAULT CONDITIONS
Lethal energy may be stored within each matrix assembly. Use extreme caution
when troubleshooting. After disconnect all sources of power, wait at least 5 minutes
for internal capacitors to discharge.
(H) - Fault triggered by hardware.
(S) - Fault triggered by software.
0000 - No Faults
No fault conditions are detected.
002C - Matrix Over-Temperature (S)
The temperature of the matrix aluminum heat sink exceeded 85°C.
Possible causes:
• External cooling fan inoperable
• Air flow on heat sink impeded due to accumulation of debris
• Operation above rated ambient temperature for an extended period of time
002E - State Machine Failure (S)
Software has encountered an undefined state.
Attempt to clear the fault by either cycling control power or pressing the black reset button in the lower
left corner of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.
002F – Parameter Out Of Date (S)
Software has determined that the system variables within the operator interface panel do not match the
ones in the PCU. Generally this fault may be cleared and normal operation resumed.
0031 - Ground Current Fault (S)
The earth safety ground current has exceeded the maximum programmed value (Max Gnd Flt I).
DOCUMENT: 151700
WARNING
PV-100208 Photovoltaic Inverter
Operation and Maintenance Manual
Copyright 2003, Xantrex Technology Inc.
5-1

Advertisement

Table of Contents
loading

Table of Contents