When you are momentarily removing power to unlock the door, as with a
mag lock, the Normally Closed and Common poles are used.
Check with local building codes for proper egress door installation.
Caution:
cause damage and premature failure of the relay. For this reason, it is recommended
that you should use either a diode or MOV (metal oxide varistor) to protect the relay.
Wire should be of sufficient gauge to avoid voltage loss.
Figure 2-7: Relay Circuit Wiring Diagram
The initial charge of the battery may take up to 24 hours to be fully charged.
Note:

2.10 Status LEDs

At power-up, LEDs 2 through 6 are turned ON then OFF in sequence.
After the above sequence has completed successfully, the PW6K1R1E goes to the
"waiting for IP address" mode.
LED
1
2
3
4
PW6K1R1E Configuration and Installation Guide, Document 800-07986V1, Revision A
Door lock mechanisms can generate feedback to the relay circuit which can
-
+
DESCRIPTION
Off-line: Off-line = 0.2 second ON, 0.8 second OFF
Waiting for IP address: 0.5 second ON, 0.5 second OFF
Flashes when data is received from either reader
Input IN1 Status: OFF = Inactive, ON = Active, Flashing = Trouble
PW6K1R1E Wiring and Setup
Diode Selection:
• Diode current rating: 1x
strike count
• Diode breakdown voltage:
4x strike voltage
NO
• For 12VDC or 24VDC
1-C
NC
strike, diode 1N4002
NO
2-C
(100V/1A) typical
NC
MOV Selection:
• Clamp voltage: 1.5x VAC
RMS
• For 24VAC strike,
Panasonic ERZ-
C07DK470 typical
NO
1-C
NC
NO
2-C
NC

Status LEDs