Accessories
The total worst case current is calculated as follows:
ANN-80 Current Draw
ANN-S/PG Current Draw
ANN-I/O Current Draw
Total Worst Case Current Draw
Using this value and referring to the Wiring Distance Table 1.1 on page 24, it can be found that the
available options are:
•
463 feet maximum using 22 Gauge wire
•
1,172 feet maximum using 18 Gauge wire
•
1,866 feet maximum using 16 Gauge wire
•
2,953 feet maximum using 14 Gauge wire
Wiring Configuration
Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
= 3 X 0.040 amps
= 1 X.0.040 amps
= 1 X.0.200 amps
ANN-BUS and power wiring are
supervised and power-limited
B A (+) (-)
TB1
4 3 2 1
ANN-BUS Device
+ - + - + -
TB3
Figure 1.3 FACP wiring to ANN-BUS Device
= 0.120 amps
= 0.040 amps
= 0.200 amps
= 0.360 amp
24 VDC
nonresettable
TB1
TB5
TB4
JP8
FACP
Product Description
ANN-BUS/
ACS BUS
A B
+ -
TB6
JP5
25