Pressure Curves - Trane 4TTL6018A1000A Installation And Operation Manual

Side discharge ac models
Table of Contents

Advertisement

Pressure Curves

490
440
390
340
290
240
190
170
165
160
155
150
145
140
135
130
125
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN.
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) LIQUID PRESSURE @ 600 CFM IS 306 PSIG
(5) SUCTION PRESSURE @ 600 CFM IS 143 PSIG
30
PRESSURE CURVES (Refer below table for models)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
(4)
(3)
50
60
70
80
OUTDOOR TEMPERATURE (Degree F)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
(5)
50
60
70
80
OUTDOOR TEMPERATURE (Degree F)
(1)
90
100
110
71
67
63
(3)
59
(1)
(1)
90
100
110
ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
(2)
OD Model
120
4TTL6018A1
4TTL6024A1
4TTL6030A1
(2)
120
18-BC98D1-1G-EN
Cooling
@SCFM
650