Pressure Curves

TEM4A0C36S41+TDR
Cooling @ 1250 SCFM
550
INDOOR ENTERING
WET BULB CURVES
500
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
450
400
350
(4)
300
250
200
40
60
170
INDOOR ENTERING
165
WET BULB CURVES
TOP TO BOTTOM
160
71, 67, 63 AND 59 DEG F.
155
150
145
(5)
140
135
130
125
120
115
110
40
60
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION PRESSURE IN LEFT
COLUMN (4).
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) DISCHARGE PRESSURE @ 1250 CFM IS 316 PSIG.
(5) SUCTION PRESSURE @ 1250 CFM IS 142 PSIG.
INTERCONNECTING LINES
GAS - 7/8" O.D.
LIQUID - 3/8" O.D.
4TWL6036A-SF-1F-EN
Figure 4. 3.0 Ton Models
(2)
(3)
(1)
80
100
120
OUTDOOR TEMPERATURE (Degree F)
(2)
(3)
(1)
80
100
120
OUTDOOR TEMPERATURE (Degree F)
TEM4A0C36S41+TDR
Heating @ 1250 SCFM
500
INDOOR ENTERING
DRY BULB CURVES
TOP TO BOTTOM
450
80, 70, AND 60 DEG F.
400
350
300
250
200
-5
5
15
25
140
INDOOR ENTERING
130
DRY BULB CURVES
TOP TO BOTTOM
120
80, 70, AND 60 DEG F.
110
100
90
80
70
60
50
40
30
-5
5
15
25
ACTUAL:
DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
DWG.NO. 4TWL6036A1
35
45
55
65
35
45
55
65
9