Refrigerant Line Considerations

Table 7.
Refrigerant Line and Service Valve Connection Sizes
Model
4TTL6018A1
4TTL6024A1
4TTL6030A1
4TTL6036A1
4TTL6042A1
4TTL6048A1
4TTL6060A1
Table 8. Factory Charge
The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested
connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via subcooling (TXV/EEV) or
superheat (fixed orifice) per the unit nameplate.
Table 9. Required Refrigerant Line Length
Determine required line length and lift. You will need this to
determine the subcooling charging corrections later in the
installation process.
Total Line Length = ___________________________Ft.
Total Vertical Change (lift) = ____________________Ft.
18-BC98D1-1G-EN
Rated Line Sizes
Vapor Line
Liquid Line
3/4
3/4
3/4
3/4
7/8
7/8
1–1/8
U U n n i i t t L L o o c c a a t t i i o o n n C C o o n n s s i i d d e e r r a a t t i i o o n n s s
Service Valve Connection Sizes
Vapor Line Connection
3/8
3/4
3/8
3/4
3/8
3/4
3/8
3/4
3/8
7/8
3/8
7/8
3/8
7/8
Liquid Line Connection
3/8
3/8
3/8
3/8
3/8
3/8
3/8
9