Communication Cables; Sensors; Controls Outputs; User Interface - Carrier AquaEdge 23XRV Controls Operation And Troubleshooting

Variable speed high-efficiency screw liquid chillers with pic6 controls
Table of Contents

Advertisement

Communication Cables

The communication transmission cables have the following elec-
trical characteristics:
2 signal conductors and one ground conductor of 20 AWG
or larger, 100% shielded
One tinned copper braid (65% coverage)
Recommended cables are shown below:
USAGE
Intra-Building
High Temperature
Plenum
Modbus Communication
To avoid potential interference, route communication cables as far
away as possible from high voltage cable and other likely distur-
bances. Always separate communication cables from other cables
and always run wiring as directly as possible.

Sensors

PRESSURE TRANSDUCERS
Pressure transducers measure and control the pressures in the unit.
These electronic sensors deliver 0 to 5 VDC. The pressure trans-
ducers are connected to the IOBs/SIOB. See Table 4.
Table 4 — Pressure Transducers
PRESSURE
TRANSDUCER
Pump Supply Pressure Measures pressure at oil pump discharge.
Pump Sump Pressure
Measures oil sump pressure.
Evaporator
Measures evaporator pressure.
Condenser
Measures condenser pressure.
Economizer
Measures economizer pressure.
(For unit with TP compressor and economizer option only.)
Evaporator Water
(Optional) Measures pressure difference between entering
Pressure Difference
and leaving water.
Condenser Water
(Optional) Measures pressure difference between entering
Pressure Difference
and leaving water.
Evaporator Entering
(Optional) Measures pressure of evaporator entering water.
Water
Evaporator Leaving
(Optional) Measures pressure of evaporator leaving water.
Water
Condenser Entering
(Optional) Measures pressure of condenser entering water.
Water
Condenser Leaving
(Optional) Measures pressure of condenser leaving water.
Water
TEMPERATURE SENSORS
The system uses electronic sensors to measure and control the
temperatures in the unit. The temperature sensors are 5K Ohm
thermistors. The temperature sensor range is –40°F (–40°C) to
245°F (118°C). See Table 5. Pressure transducers and thermistors
can be calibrated in the Quick Test Menu. Pressure transducers
can be adjusted up to 5 psi (34.5 kPa) and thermistors can be ad-
justed up to ±5°F (2.8°C).
CABLE
Belden 8772
Belden 85240
Belden 89418
Belden 3106A
PURPOSE
Table 5 — Temperature Sensors
TEMPERATURE SENSOR
Entering Chilled Water
Leaving Chilled Water
Entering Condenser Water
Leaving Condenser Water
Evaporator Refrigerant
Liquid
Compressor Discharge
Oil Sump
Vaporizer Temperature
Chilled Water Supply (Optional)
Chilled Water Return (Optional)
Motor Winding
Economizer Gas
NOTE(S):
a. Separate inputs used when the chiller is in network mode.

Controls Outputs

EVAPORATOR/CONDENSER WATER PUMP
The controller regulates the evaporator/condenser water pump.
Note that Carrier requires full or parallel pump control since Carri-
er controls utilize the pumps for freeze protection and high pres-
sure control.
ENVELOPE/HGBP CONTROL VALVE
The on/off HGBP valve artificially loads the chiller and keeps it
running under low load conditions.
VFD
The VFD modifies motor frequency to allow compressor start-up
and capacity control. The VFD controls continually monitor pa-
rameters to ensure compressor protection. If a problem occurs, the
controller triggers an alarm and the compressor is stopped.

USER INTERFACE

The PIC6 Human Machine Interface (HMI) is a color 10.4-in.
TFT touch screen. Navigation is either direct from the touch
screen interface or by connecting to a web interface at the Ethernet
IP port of the controller. The navigation menus are the same for
both connection methods.

Web Connection

Two web connections may be authorized at the same time. When
two users are connected simultaneously, there is no priority be-
tween users; that is, the last modification is in effect regardless
of the user. Connection is from a personal computer using a
Java-enabled web browser. See "CONTROLLER SETTINGS"
on page 34 for configuration instructions.
The minimum browser configuration includes:
Microsoft Internet Explorer (version 8 or higher) or Mozilla
Firefox (version 3.5.2 or higher). In the advanced connection
options, add the unit address to the address list. Do not use a
proxy server.
Java platform (version 6 or higher). In the control panel,
deselect (uncheck) the option that allows storing tempo-
rary internet files and use a direct connection.
To access the PIC6 user interface, enter the IP address of the unit
in the address bar of the web browser. The IP address can be
viewed or changed from the PIC6 interface. For more information
on the web browser and Java platform configuration, see "DIAG-
NOSTICS AND TROUBLESHOOTING" on page 25.
11
PURPOSE
Measures entering evaporator water
temperature
Measures leaving evaporator water temperature
Measures entering condenser water
temperature
Measures leaving condenser water temperature
Measures evaporator refrigerant liquid
temperature
Measures compressor discharge temperature
Measures oil sump temperature
Measures temperature of oil leaving vaporizer
a
Measures temperature of chilled water supply
Measures temperature of chilled water return
a
Measures temperature of each phase of
compressor motor
Measures gas temperature from economizer to
compressor (For unit with TP compressor and
economizer option only)

Advertisement

Table of Contents
loading

Table of Contents