4 SETTINGS AND PROCEDURES FOR OPERATION

4.5.1 Slave registration

RUN
U ASI
CM
PRG ENA.
ERR.
S ERR.
CODE
MODE
SET
Press the MODE switch
until the CM LED turns on.
RUN
U ASI
CM
ERR.
CODE
MODE
SET
Press the MODE switch
until the CM LED turns off.
RUN
U ASI
CM
ERR.
CODE
MODE
SET
Press the MODE switch and SET
switch simultaneously until
"gd" appears on the CODE LED.
4 - 10
Downloaded from
ManualsNet.com
The configuration data of the slaves must be registered to the QJ71AS92 before it is
operated in the protected operation mode.
Slave registration to the QJ71AS92 can be performed by the switch operation in the
following (1) and (2).
However, the data registered to the QJ71AS92 are lost when the programmable
controller is powered on or the CPU module is reset. To store the registered data,
perform operation up to (3). The data are written to the EEPROM of the QJ71AS92.
(1) Put the QJ71AS92 in the configuration mode and assign
addresses to the slaves.
If the CM LED is off, press the MODE switch until the CM LED is lit.
Alternatively, turn Y16 ON.
In this mode, assign any slave address to the slave of slave address 0. (Refer to
A
B
"Section 4.5.2 Slave address assignment".)
TIP
When assigning the slave address with the QJ71AS92 connected to the slave of
slave address 0, please make sure that only one slave of slave address 0 is
connected to it.
The QJ71AS92 will not perform slave address assignment when being connected
with more than two slaves of slave address 0
(2) Put the QJ71AS92 in the protected operation mode and register the
configuration data of the slaves.
PRG ENA.
S ERR.
Press the MODE switch until the CM LED is off. Alternatively, turn Y17 ON.
Normally, set this mode when operating the AS-i system.
A
B
If the MODE switch is not pressed until CM LED turns off, the configuration data
of the slaves is not registered properly even though CM LED is on. If the
ERR.LED is lit, restart operation from (1).
(3) Press the MODE and SET switches simultaneously until "gd"
appears on the CODE LED. Alternatively, turn Y1C ON. (The
PRG ENA.
S ERR.
configuration data are written to the EEPROM.)
A
B
search engine
MELSEC-Q
4 - 10

Advertisement

Table of Contents
loading

Table of Contents