Panasonic CS-A181KR Service Manual page 5

Table of Contents

Advertisement

Functions
Outdoor Unit
4-Way Valve Control
• When the unit is switched to "OFF" during
Heating operation, 4-way valve stays at
Heating Position for 5 minutes.
Overload Protector
• Inner protector (Compressor, Fan Motor).
60 Secs. Forced Operation Control
• Once the compressor is activated, it does
not stop for 60 secs. (Stops immediately
with remote control stop signal.)
Outdoor Fan Operation Control
• 4-pole induction motor (2-speed)
• For Cooling or Soft Dry Operation
Hi-speed ... when outdoor temperature
Lo-speed ... when outdoor temperature
• For Heating Operation
Hi-speed ... when outdoor temperature
Lo-speed ... when outdoor temperature
• For Over-heating Protection, the Fan is
switched ON or OFF depending on the
piping temperature and the outdoor tem-
perature.
Deice Control
• To prevent frosting at outdoor heat
exchanger during Heating Operation.
reaches to 31°C
reaches to 29°C
reaches to 13.5°C.
reaches to 15.5°C.
2-Way Valve Control
• 2-way valve is ON for 1 minutes after
compressor start. Other than this, 2-way
valve is OFF. (A241K only)
– 4 –
CS-A181KR