Toshiba RAV-SP122AT2P-UL Installation Manual page 14

Outdoor unit
Table of Contents

Advertisement

How to wire
1. Remove the terminal cover by taking off the mounting screw (1 piece).
2. Connect the power supply wires and system interconnection wires to the terminal block of the electrical control
box.
3. Tighten the screws of the terminal block, connect the wires matching the terminal numbers (Do not apply
tension to the connecting section of the terminal block.)
4. Attach the terminal cover.
• When connecting the system interconnection wire to the outdoor unit terminal, prevent water from coming into
the outdoor unit.
• Insulate the unsheathed cords (conductors) with electrical insulation tape. Process them so that they do not
touch any electrical or metal parts.
• For system interconnection wires, do not use a wire joined to another on the way.
Use wires long enough to cover the entire length.
Terminal cover
Stripping length power cord and connecting wire
0.39" (10)
L1
L2
1.57"
(40)
Ground wire
System interconnection wire
25-EN
Screw
L1
L2
S
L1
Earth screw
System interconnection wire
0.39" (10)
S
L1
L2
0.39" (10)
0.39" (10)
1.57"
1.18"
1.18"
(40)
(30)
(30)
(in (mm))
Ground wire
Power supply wire
� 13 �
 Wiring
All wiring and connections must comply with NEC,
CEC, local codes.
1. Connect all wires to the correct terminal on the
wiring terminal blocks.
2. Make sure that all connectors are secure.
3. Size connectors per the ratings listed in the system
requirement section.
4. System interconnections should be minimum,
16 AWG.
 Connecting power and control
cables (Field supplied)
• The main power is supplied to the outdoor unit.
The field supplied connecting cables from the
outdoor unit to the indoor unit consist for 4 wires and
provides the power for the indoor unit as well as the
communication signal between the outdoor and
indoor unit.
L2
• Consult local building codes, NEC (National
Electrical Code) or CEC (Canadian Electrical Code)
for special requirements.
• The following are the electrical requirements.
Model RAV-
Power supply
MCA
MOCP (MAX Fuse/CB)
Breaker
Field power supply wires
System interconnection wires
Power supply wire
MCA = Minimum Circuit Amps
MOCP = Maximum Over Protection Device Amps.
SP122, 182
208/230V, 60Hz
14A
20A
15A
AWG14
AWG16
26-EN