USE THE FOLLOWING PRECAUTIONS WHEN HANDLING WAX-COATED SPRINKLERS
Many of Viking's sprinklers are available with factory-applied wax coating for corrosion resistance. These sprinklers MUST receive
appropriate care and handling to avoid damaging the wax coating and to assure satisfactory performance of the product.
General Handling and Storage of Wax-Coated Sprinklers:
Store the sprinklers in a cool, dry place (in temperatures below the maximum ambient temperature allowed for the sprinkler temperature rating. Refer
to Table 1 below.)
Store containers of wax-coated sprinklers separate from other sprinklers.
Protect the sprinklers during storage, transport, handling, and after installation.
Use original shipping containers.
Do not place sprinklers in loose boxes, bins, or buckets.
Installation of Wax-Coated Sprinklers:
Use only the special sprinkler head wrench designed for installing wax-coated Viking sprinklers (any other wrench may damage
the unit).
Take care not to crack the wax coating on the units.
For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after
sprinkler installation to protect the corrosion-resistant properties of the sprinkler.
Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they would be exposed to temperatures exceed-
ing the maximum recommended ambient temperature for the temperature rating used.
Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant coating. Thereafter, inspect representative
samples of the coated sprinklers in accordance with NFPA 25. Close up visual inspections are necessary to determine whether the sprinklers are being
affected by corrosive conditions.
Sprinkler Temperature Rating
(Fusing Point)
155 °F (68 °C) / 165 °F (74 °C)
175 °F (79 °C)
200 °F (93 °C)
220 °F (104 °C)
286 °F (141 °C)
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
1
Jurisdiction. Refer to specific installation standards.
Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambi-
ent temperature allowed.
Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data
pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.
vikinggroupinc.com.
Form No. F_091699
18.10.11
BULLETIN
TABLE 1
Wax Part
Wax Melting Point
Number
02568A
04146A
04146A
02569A
02569A
Rev 16.1.P65
Maximum Ambient
Ceiling Temperature
148 °F (64 °C)
100 °F (38 °C)
161 °F (71 °C)
150 °F (65 °C)
161 °F (71 °C)
150 °F (65 °C)
170 °F (76 °C)
150 °F (65 °C)
170 °F (76 °C)
150 °F (65 °C)
Replaces Form No. F_091699 Rev 16.1
Page 4 of 4
CARE AND HANDLING
OF SPRINKLERS
Wax Color
1
Light Brown
Brown
Brown
Dark Brown
Dark Brown
(Added P65 Warning)