Logical Flow Diagrams; High Voltage Logical Flow; Control Logical Flow - Trane Arctic Thermafit AXM Installation, Operation And Maintenance Manual

Air-to-water heat pump
Table of Contents

Advertisement

Logical Flow Diagrams

The following section presents the simplified logical flow
block diagrams for the principal systems in the AXM air-to-
water modular heat pump.

High Voltage Logical Flow

AXM heat pump models are available in a range of voltage/
amperage/phase configurations to meet the demands of a
Figure 24. High voltage logical flow of single module
460 VAC, 60 HZ, 3 PHASE
MOP 124A, MCA 90A
SELECT CONDUCTOR SIZE RATED @ 75°C
PDB1
40A
CB1
40A
CB2
MS1
MS2
M1A
M2A
OL1
OL2
M1
M2
REFRIGERATION
REFRIGERATION
COMPRESSOR
COMPRESSOR
15T/15HP
15T/15HP
460V, 3PH, 60 Hz
460V, 3PH, 60 Hz
38.6 RLA (1.4)
38.6 RLA (1.4)
34.6 RLA (1.56)
34.6 RLA (1.56)
174 LRA
174 LRA

Control Logical Flow

The heat pump uses low voltage for controller and sensor
circuits. See following figure.
62
2A
FU1
2A
FU2
2A
FU3
MS1
MS1
MS2
HTR1A
HTR2A
HTR3A
HTR1
HTR2
HTR3
REFRIG COMP M1
REFRIG COMP M1
REFRIG COMP M2
CRANKCASE HEATER
ACCUMULATOR HEATER
CRANKCASE HEATER
ACCUMULATOR HEATER
460V
460V
460V
93VA
93VA
93VA
HEAT TAPE POWER SUPPLY
FROM DISTRIBUTION PANEL
120 VAC, 60 HZ, 1 PHAS
PDB2
worldwide market. The high voltage configuration for a heat
pump module is listed on each module's name plate. The
heat pump is designed to operate with high voltage power
supplied to the unit at all times. See
2A
FU4
3A
FU5
3A
FU6
MS2
HTR4A
INPUT: 200-500VAC
1.9A
HTR4
250 VA
24V DC
XF1
PWS1
480/24 VAC
POWER SUPPLY
OUTPUT: 24VDC
10A
REFRIG COMP M2
460V
TO 24V AC
TO 24V DC
93VA
DEVICES
DEVICES
HTC
X WATTS
HEAT
TAPE
Figure 24, p. 62
10A
FU7
10A
FU8
M3A
M4A
M3
M4
VM1
3-PH
FB1
FB1
PHASE
FAN #1
FAN #2
MONITOR
EC AXIAL FAN
EC AXIAL FAN
400 - 480 VAC
*PRIMARY
460V, 3PH, 60 Hz
460V, 3PH, 60 Hz
MODULE
5.0 FLA
5.0 FLA
ONLY*
1195 RPM
1195 RPM
ARTC-SVX006A-EN