Heat Pump Performance Data
Table 9. Typical AXM air-to-water heat pump selection of two 30 ton modules (continued)
Input Power at Full Load
Compressors
Fans
Electrical performance per power supply
Number of power supplies
Modules per power supply
Power supply
46
73.97 kW
55.3 A
4.5 A
1
1
460/3/60 V-ph-Hz
Chiller MCA
Chiller MOCP
Chiller FLA
Chiller MCA
Chiller MOCP
68.0 A
100.0 A
119.7 A
128.0 A
150.0 A