Troubleshooting

CHECKING FOR LEAKS

Use this illustration as a guide when checking for sources of water leakage. You or your dealer may be able to correct what appears to
be a problem.
Water leaks which appear at the water heater bottom or on the surrounding floor may be caused by condensation, loose connections or
relief valve operation and leakage. Do not replace the water heater until full inspection of all potential leak points is made and corrective
steps taken to stop the leak.
Leakage from other appliances, water lines, or ground should also be suspected until proven otherwise.
2
1
10
9
Figure 10. Leakage Checkpoints
Read and understand this instruction
manual and the safety messages
herein before installing, operating or
servicing this water heater.
Failure to follow these instructions and
safety messages could result in death
or serious injury.
This manual must remain with the
water heater.
42 • Commercial Electric Water Heaters
Never use this water heater unless it is completely filled with water.
To prevent damage to the tank, the tank must be filled with water.
2
Water must flow from the hot water faucet before turning the water
heater.
3
1.
Where possible remove or lift top cover to examine threads of
fittings installed into tank for evidence of leakage. Correct fitting
leaks as necessary.
2.
*The anode rod fitting may be leaking.
3.
*The temperature-pressure relief valve may be leaking at the
tank fitting.
4.
Water on the side of the tank may be condensation due to the
panel or insulation not being in place.
4
5.
Defective element which leaks at terminals or thru flange. Replace
element*
6.
Loose element/gasket leak
1) Screw-in type: tighten with 1-1/2" socket wrench. If leak
5
6
2) Flange type: tighten screw with wrench. If leak continues
7
7.
Small amounts of water from temperature-pressure relief valve
may be due to thermal expansion, high water pressure in your
area, or a defective temperature-pressure relief valve.
8.
All water which appears at the heater bottom or on the surrounding
floor may be caused by condensation, loose connections or relief
8
valve operation and leakage. Do not replace the heater until a
full inspection of all potential leak points is made and corrective
steps taken to stop the leak.
9.
Water from a drain valve may be due to the valve being slightly
opened.
10. *The drain valve may be leaking at the tank fitting.
Leakage from other water heaters, water lines, or ground seepage
should also be checked.
*
To check where threaded portion enters tank, insert cotton
swab between jacket opening and fitting. If cotton is wet,
follow instructions in Draining the Water Heater (page 36)
and then remove fitting. Put pipe dope or teflon tape on the
threads and replace. Then follow the instructions in Installing
the Water Heater (page 12) and Start Up and Operation (page
17) .
*
Contact your dealer as it is necessary to shut off electricity
and drain tank to perform procedure.
continues, remove element*, discard gasket and clean thread
areas. Apply non-hardening Permatex Number 2 to thread
areas, install new gasket and screw element into fitting until
it seats. Tighten 1/2 to 3/4 turn with wrench.
remove element* and discard gasket. Clean gasket seating
areas and re-install element with new gasket. A new element
may be required where threads have become rusted or
damaged, preventing tightening.