5.13 Continuity Checks

WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.
cause severe injury or death.
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Short circuits.
Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Note: Disconnect the generator set battery before
performing continuity checks to prevent damage
to the ohmmeter.
TP-6198 3/15
the
generator
set.
Accidental starting can
Before working on the
Do not contact electrical
To further check generator set components, disconnect
the battery and remove wiring harness plugs from the
controller circuit board. Refer to the wiring diagrams in
the wiring diagram manual and use an ohmmeter to
check for continuity and good ground connections. A
zero reading on the ohmmeter indicates continuity. No
ohmmeter reading indicates very high resistance or an
open circuit.
Figure 5-19 illustrates the generator set master switch
continuity with the switch in the RUN and AUTO
positions.
Master Switch in
RUN Position
Master Switch in
AUTO Position
Figure 5-19 Generator Set Master Switch Continuity
Checks (back view of switch)
Section 5 Component Testing and Adjustment
Zero ohms (continuity) across RUN
and COM terminals
Zero ohms (continuity) across
COM and AUTO terminals
tp6196