5-4 Selection of control power supply

For the control power supply of MDS-R Series, choose the stabilized power supply that satisfies the
specifications below.
(1) Power supply specification
CAUTION
Downloaded from
ManualsNet.com
24VDC ±10%
Output voltage
200mV max.
Ripple
Select the external power supply unit that satisfies the current or rush
current specification of the drive unit control power supply
specification.
Output current
If the power supply is supplied to multiple drive units, select a product
that satisfies the total of the drive units.
Circuit
protector
DC24V
Stabilized power supply
ACIN
Circuit protector
or
Protection fuse
DCOUT
1. Do not damage, apply excessive stress, place heavy things on or sandwich
the cables, as this may lead to electric shocks.
2. Separate the signal wire from the drive line/power line when wiring.
3. Do not connect or disconnect the connection cables between each unit while
the power is ON.
search engine
5. Peripheral Devices
External power supply unit
5 - 7
Servo drive unit
MDS-R
CN22