Superior Fireplaces Custom WRT40STWS Assembly, Installation And Operation Instructions page 11

Multi-sided wood burning fireplace
Table of Contents

Advertisement

Storm Collar
Flashing
Cone
Nail Only Outer
Perimeter of
Flashing
Underlap Shingles
at Bottom
Figure 24 - Flashing Installation
STORM COLLAR INSTALLATION (SC-10)
Place storm collar over pipe and slide down until it is snug against
the open edge of the flashing (see Figures 24 and 25). Apply water-
proof caulking to all seams and notches around storm and also at
base around shingles.
Chimney
Pipe
Storm
Collar
Figure 25 - Storm Collar
TERMINATIONS
Standard Installation
The fireplace system must be terminated with the listed round top or
chase terminations. In any case, refer to the installation instructions
supplied with the termination.
Terminations approved for this fireplace are RLT-12D, which can be
used for flashing or chase and STL-12D for chase style termination
only. Figure 26, shows an RLT-12D round top termination.
Follow installation instructions provided with termination being used.
CAUTION: Do not seal openings on the rooftop
flashing. Follow the installation instructions provided
with the termination being used.
126613-01B
VENTING INSTALLATION Continued
Overlap
Shingles Top
and Sides Only
Overlap
Shingles (Top and
Sides of Flashing Base)
Waterproof
CHASE INSTALLATIONS
Caulk
Instructions for chase installations are included with the chase style
termination chosen. In a multiple chase installation, be sure to provide
Flashing
adequate distance between terminations to prevent smoke spillage
from one termination to another. Terminations must be separated a
minimum of 30" center to center and stacked at a minimum vertical
height difference of 18" (see Figure 27).
Note: If a decorative shroud is to be installed, contact the manufac-
turer for specifications.
Superiorfireplaces.US.com
Stainless
Inner Flue
Pipe
Secure
Termination
to Outer
Pipe with 3
Screws
Figure 26 - Terminations
30" Min.
30" Min.
Figure 27 - Multiple Chase Installation
RLT-12D
Chase
Top
Screen
1" Non-
com-
bustible
1"
Spacer
Space
Apply
Waterproof
Caulking
Storm
Collar
Flashing
Underlap
Shingles
18"
Min.
Typ.
11