International comfort products G9MVE A3 Series Installation Instructions Manual page 11

Variable speed motor, two-stage 35” tall, high efficiency condensing gas furnace
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Table 3
Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS
(1 SQ. IN./2,000 BTUH)
FURNACE
(1,100 SQ. MM/KW)
INPUT
(BTUH)
Free Area of Open-
ing and Duct
Sq. In (Sq. mm)
20 (12904)
40,000
30 (19355)
60,000
40 (25807)
80,000
50 (32258)
100,000
60 (38709)
120,000
70 (45161)
140,000
EXAMPLE: Determining Free Area
FURNACE
WATER HEATER
100,000
+
30,000
60,000
+
40,000
80,000
+
30,000
Table 4
Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
30
ACH
1,050
0.60
(29.7)
1,260
0.50
(35.6)
1,575
0.40
(44.5)
2,100
0.30
(59.4)
3,150
0.20
(89.1)
(118.9)
6,300
0.10
(178.0)
(237.8)
NP
0.00
NP = Not Permitted
Air for Combustion, Ventilation,
Figure 6
and Dilution for Outdoors
*Minimum dimensions of 3‐in. (76mm)
NOTE: Use any of the following combinations of openings:
A & B, C & D, D & E, F & G
440 01 4401 02
Round Duct
Free Area of Open-
In. (mm)
Dia
5 (127)
6 (152)
7 (178)
8 (203)
9 (229)
10 (254)
TOTAL INPUT
= (130,000 divided by 4,000)
= (100,000 divided by 3,000)
=
(110,000 divided by 2,000)
40
50
1,400
1,750
1,400
(39.6)
(49.5)
(39.6)
1,680
2,100
1,680
(47.5)
(59.4)
(47.5)
2,100
2,625
2,100
(59.4)
(74.3)
(59.4)
2,800
3,500
2,800
(79.2)
(99.1)
(79.2)
4,200
5,250
4,200
(148.6)
(118.9)
8,400
10,500
8,400
(297.3)
(237.8)
NP
NP
L12F012
Specifications subject to change without notice.
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Round Duct
ing and Duct
In. (mm)
Sq. In (Sq. mm)
Dia
14 (8696)
5 (127)
20 (13043)
5 (127)
27 (17391)
6 (152)
34 (21739)
7 (178)
40 (26087)
7 (178)
47 (30435)
8 (203)
= 32.5 Sq. In. for each two Vertical Ducts or Openings
= 33.3 Sq. In. for each Single Duct or Opening
= 55.0 Sq. In. for each two Horizontal Ducts
FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
40
60
80
3
3
Space Volume Ft
(M
)
1,500
2,000
(42.5)
(56.6)
1,800
2,400
(51.0)
(67.9)
2,250
3,000
(63.7)
(84.9)
3,000
4,000
(84.9)
(113.2)
4,500
6,000
(127.3)
(169.8)
9,000
12,000
(254.6)
(339.5)
NP
NP
NP
Air for Combustion, Ventilation,
Figure 7
and Dilution from Indoors
* Minimum opening size is 100 sq in. (64516 sq. mm) with
minimum dimensions of 3‐in. (76mm)
{ Minimum of 3‐in. (76mm) when type‐B1 vent is used.
CONDENSATE TRAP
Gas Furnace: (F/G)9MVE
TWO OPENINGS OR
VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Free Area of Opening
Round Duct
and Duct
In. (mm) Dia.
Sq. In (mm)
10 (6452)
4 (102)
15 (9678)
5 (127)
20 (12904)
5 (127)
25 (16130)
6 (152)
30 (19355)
6 (152)
35 (22581)
7 (178)
100
120
2,500
3,000
3,500
(70.8)
(84.9)
(99.1)
3,000
3,600
4,200
(84.9)
(101.9)
(118.9)
3,750
4,500
5,250
(106.1)
(127.3)
(148.6)
5,000
6,000
7,000
(141.5)
(169.8)
(198.1)
7,500
9,000
10,500
(212.2)
(254.6)
(297.1)
15,000
18,000
21,000
(424.4)
(509.2)
(594.1)
NP
NP
140
NP
L12F013
11