Part II - Venting Specifications for:
40 Gallon (151.4 L)
50 Gallon (189.2 L)
60 Gallon (227.1 L)
This w ater heater is a pow er vented appliance and is designed to vent its
products of combustion through 2'' (5.1 cm) or 3'' (7.6 cm) diameter vent
pipe to the outdoors. The w ater heater may be either vented horizontally
through the w all or vertically through the roof. Use a 3'' (7.6 cm) to 2''
(5.1 cm) reducer to connect to the vent outlet w hen using 3'' (7.6 cm)
vent pipe. Apply proper cement at joint locations. Table 5 lists the
maximum vent lengths for this w ater heater using 2'' (5.1 cm) vent pipe. If
possible, locate the w ater heater so that the venting length and number of
elbow s are kept to the minimum distance necessary to reach the outside. If
the installation requires venting lengths that exceed the lengths listed for
2'' (5.1 cm) vent pipe in Table 5 then use 3'' (7.6 cm) vent pipe for the
vent connector.
Table 6 lists the venting distances allow ed w ith 3'' (7.6 cm) diameter vent
pipe. When venting with 3'' (7.6 cm) vent pipe, use a 3'' (7.6 cm) to 2''
(5.1 cm) reducer to exit through the building w all w ith 2'' (5.1 cm) vent
pipe. Use the 2'' (5.1 cm) vent terminal supplied w ith the w ater heater to
terminate on the outside of the building. If the length of the 2'' (5.1 cm)
needed to go through the w all is greater than 14'' (35.6 cm), use 3'' (7.6
cm) vent pipe to go through the w all and reduce to 2'' (5.1 cm) vent pipe
immediately after exiting the outside w all. Refer to the venting illustrations
on the follow ing pages. Make sure the vent pipe terminal is at least 1'' (2.5
cm) aw ay from the edge of the w all.
VENT CONNECTOR LENGTHS FOR 2'' (5.1cm) DIAMETER VENT PIPE
Terminating
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
Through the Roof
TABLE 5
# of 90° Elbows
(excluding vent
terminal)
1
2
3
4
0
1
2
3
4
19
Max straight
Length
ft (m)
45 (13.7)
40 (12.2)
35 (10.7)
30 (9.1)
50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)
30 (9.2)
Min straight
Length
ft (m)
2 (.6)
2 (.6)
2 (.6)
2 (.6)
7 (2.1)
7 (2.1)
7 (2.1)
7 (2.1)
7 (2.1)