Parameter Defaults and Descriptions
Item
Parameter name
Mode
Setting Change Protection
Protec-
tion
Mode
Setting Value Change
Prohibition
Burnout Alarm
Value 1
Adjust
Burnout Alarm
Mode
Value 2
Voltage Fluctuation
Compensation Standard Value
All Initialization
Set Value Initialization
Processing Value Initialization
Alarm Hysteresis 1
Alarm Hysteresis 2
Gate Input Function
Voltage Fluctuation
Compensation Reference Value
Startup Lock Time
Output ON-Delay
Soft Startup Time
SSR Short Circuit Detection
SSR Open Circuit Detection
Heater Layer Short Circuit
Detection (Overcurrent
Detection)
Heater Layer Short
Circuit Alarm Level
(Overcurrent Alarm
Set Value)
Heater Control Method *1
Set Mode
Switchable Display
Power Save Mode
Power Save Mode Standby Time Sets the time to enter power save mode.
Display Mode
Display Refresh Time
Unit Number
Baud Rate
Data Length
Stop Bits
Parity Bit
Gate OFF output hold time *2
Number of CT passes 1
CT Ratio 1
Setting 1 for number of effective
digits to be displayed after the
decimal point
Number of CT passes 2
CT Ratio 2
Setting 2 for number of effective
digits to be displayed after the
decimal point.
Gate
Gate Current Level *1
Mode
*1. Displayed by the K8AC-H@@P@-FLK.
*2. Displayed by the K8AC-H@@C@-FLK.
18
Restricts access to Adjust Mode or Set Mode from Run Mode.
0: Access enabled to both Adjust Mode and Set Mode.
1: Access enabled to Adjust Mode and disabled to Set Mode.
2: Access disabled to both Adjust Mode and Set Mode.
Prohibits changes to set values.
K8AC-H@1 Sets the output operation value for the burnout alarm.
K8AC-H@2
The burnout alarm function can be disabled by setting the set value to
"−".
K8AC-H@3
K8AC-H@1 Sets the output operation value for the burnout alarm.
K8AC-H@2
The burnout alarm function can be disabled by setting the set value to
"−".
K8AC-H@3
Sets the standard voltage used by the voltage fluctuation
compensation function. The fluctuation compensation function
operates in respect to this set value.
Returns all set values and measurement values to their default
settings.
Returns all set values to their default settings.
Returns all measurement values to their default settings.
Sets hysteresis for the alarm output value for burnout detection
(undercurrent) and heater layer short circuits (overcurrent) for CT1.
Sets hysteresis for the alarm output value for burnout detection
(undercurrent) and heater layer short circuits (overcurrent) for CT2.
Turns the gate input function ON and OFF. If the gate input is turned
OFF, application as a simple ammeter is possible.
Turns the voltage fluctuation compensation function ON and OFF.
Sets the lock time for the startup lock.
Sets the output delay time. Set this parameter to set the operating time.
Sets the soft startup time. Set this parameter only when using a soft
start function with the power regulator.
Turns the SSR short circuit detection function ON and OFF.
Turns the SSR open circuit detection function ON and OFF.
Turns the heater layer short circuit (overcurrent) detection function ON
and OFF.
K8AC-H@1 Sets the operating level for heater layer short circuit (overcurrent)
alarms.
K8AC-H@2
The heater layer short circuit alarm level is the same for both CT1 and
K8AC-H@3
CT2.
Sets the control method of the cyclic/phase control heater.
Sets the CT for which to normally display the current.
Turns entering the power save mode ON and OFF.
Sets a 7-segment (NORM). full-span comparison (CMP), or bar (BAR)
display.
Sets the refresh time for the display.
Sets the unit number for RS-485 communications.
Sets the baud rate for RS-485 communications.
Sets the data length for RS-485 communications.
Sets the number of stop bits for RS-485 communications.
Sets the parity for RS-485 communications.
Sets the time from when the gate signal goes OFF until the burnout
alarm output turns OFF.
Sets the number of times the conductor for CT1 is passed through the
current transformer.
Sets the CT ratio for CT1.
Sets the number of effective digits to be displayed after the decimal
point for the CT1 current display.
Sets the number of times the conductor for CT2 is passed through the
current transformer.
Sets the CT ratio for CT2.
Sets the number of effective digits to be displayed after the decimal
point for the CT2 current display.
Sets the gate current value that stops an alarm, detection, or output.
(This setting is only valid when phase control is selected as the heater
control method.)
Note:
Shaded parameters must always be set regardless of the
measurement method.
Description
Param-
Setting range
eter
aspt
0 to 2
0
wtpt
ON/OFF
OFF
0.200 to 2.200 A
1.000 A
al-1
2.00 to 22.00 A
10.00 A
20.0 to 200.0 A
100.0 A
0.200 to 2.200 A
1.000 A
al-2
2.00 to 22.00 A
10.00A
20.0 to 200.0 A
100.0 A
vfcv
100 to 240 VAC
100 V
init
ON/OFF
OFF
sini
ON/OFF
OFF
pini
ON/OFF
OFF
hys1
1 to 999
10
hys2
1 to 999
10
gate
ON/OFF
ON
comp
ON/OFF
OFF
stim
0 (OFF) to 255 s
0 (OFF)
odly
0.0 (OFF) to 99.9 s
0.0 (OFF)
soft
0.0 (OFF) to 99.9 s
0.0 (OFF)
ssht
ON/OFF
OFF
sopn
ON/OFF
OFF
hrst
ON/OFF
OFF
0.200 to 2.200 A
2.000 A
2.00 to 22.00 A
20.00 A
hral
20.0 to 200.0 A
200.0 A
msmd
PH1, PH3, CYCL
PH1
dsel
CT1, CT2
CT1
psmd
ON/OFF
OFF
pstm
10 to 300 s
60 s
dsmd
NORM, CMP, BAR
NORM
dsrf
0.2 s, 0.5 s, 1.0 s, FAST 0.5 s
u no
0 to 64
0
1200, 2400, 4800, 9600,
dps
9600
19200
len
7, 8
7
sbit
1, 2
2
prty
EVEN, ODD, NONE
EVEN
goht
0 to 999 s
2 s
nct1
1 to 99 times
1 time
ctr1
1 to 999
1
Depends
ndp1
0 to 3 places
on the
model.
nct2
1 to 99 times
1 time
ctr2
1 to 999
1
Depends
ndp2
0 to 3 places
on the
model.
g-lv
7.0 to 20.0 mA
7.0 mA