Installation

Receiving the Equipment

Your system has been tested and inspected prior to
shipment. To ensure that your equipment is received in
excellent condition, make a visual inspection of the
equipment immediately upon delivery. Carefully remove
the shipping container and all protective packaging. Open
the electric box and thoroughly inspect the unit for any
signs of transit-incurred damage. If there is shipping
damage, it must be noted on the freight carrier's delivery
forms before signing for the equipment. Any freight
claims must be done through the freight carrier.
Trane ships all equipment FOB factory. Trane is not liable
for any equipment damage while in transit. Trane can
assist in the claim filing process with the freight carrier.
Should any damage be present, notify Trane Product
Support prior to attempting any repairs. Check the
equipment against the packing slip to see if the shipment
is complete. Report any discrepancies to the appropriate
authority.
A Data Package has been sent with your unit. It contains
this manual, system drawings, applicable SSDs and other
appropriate instructions based on the configuration of
your unit and options selected. The data package has been
shipped with your unit in a clear plastic bag. These
documents need to be kept with the unit for future
reference.

Site Preparation

Our Air-cooled Condensers are designed with easy service
access in mind. Install the condenser in a secure location
where it cannot be tampered with and the main power
disconnect switch cannot be inadvertently turned Off.
Allow access to the unit for routine operation, servicing
and for necessary maintenance. The components on
outdoor condensers are accessed through the top by
removing the fan assembly panel.
The electric box is accessed at the header end of the unit.
Locate the unit where the fan(s) are not likely to draw dirt
and debris into the coil fins. Refer to the installation
drawing provided with your unit for the dimensions.
The condenser must be kept level to operate properly.
Note: Working clearance requirements need to be
established prior to mounting the unit. Refer to
local and national electrical codes.
10

Rigging

WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could
result in unit dropping and possibly crushing operator/
technician which could result in death or serious injury,
and equipment or property-only damage.
Test lift unit approximately 24 inches (61 cm) to verify
proper center of gravity lift point. To avoid dropping of
unit, reposition lifting point if unit is not level.
WARNING
Heavy Object!
Failure to follow instructions below could result in unit
dropping which could result in death or serious injury,
and equipment or property-only damage.
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift.
The unit must be lifted vertically and kept in a level
position. Move the unit with a suitable device such as a
forklift or attach an overhead lifting sling. The unit may be
lifted with an overhead sling attached to the top of the
mounting support legs. Use an appropriate lifting device
that has the capacity to safely handle the weight of the
equipment. A weight table is provided on the installation
drawing supplied with your unit. If using an overhead
lifting device, use spreader bars that exceed the cabinet
width to avoid crushing the sides of the unit.
Remote condensers are shipped on a skid to facilitate
moving prior to installation. The unit should always be
stored in a dry location prior to installation. To prevent
damage when lifting the unit, all available lifting eyes on
the cabinet must be used.
Note: Ensure the mounting legs are fully extended when
the unit is raised.