Installation of indoor unit
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring
points on the wall.
2) Secure the mounting plate to the wall with screws.
Floor Installation
6screws
3) Once refrigerant piping and drain piping connections are complete, fill in the gap of the through hole with putty. A gap
can lead to condensation on the refrigerant pipe, and drain pipe, and the entry of insects into the pipes.
4) Attach the front panel and front grille in their original positions once all connections are complete.
Flaring the pipe end
1)Cut the pipe end with a pipe cutter.
2)Remove burrs with the cut surface facing downward so that the chips do not enter the pipe.
3)Fit the flare nut on the pipe.
4)Flare the pipe.
5)Check that the flaring is properly made.
WARNING
1) DO not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which had been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
Cut exactly
Renove
at right
burrs
angles
Casing
Flaring
Set exactly at the position shown below
Flare tool for R410A
A
Clutch-type
Die
A
0-0.5mm
Wall Installation
Conventional flare tool
Clutch-type
Wing-nut type
(Rigid-type)
(lmperial-type)
1.5-2.0mm
1.0-1.5mm
24
INSTALLATION INSTRUCTIONS
6screws
The pipe end must
Flare's inner
be evenly flared in
surface must
a perfect circle
be scratch-free
Make sure that the
flare nut is fitted
Molding