Kidde FX-270 Installation Sheet page 2

Single action pull station

Advertisement

Figure 4: Pull station wiring
(1) SLC in - from previous device or control panel
(2) SLC out - to next device or EOLR
Specifications
Voltage
IDC maximum
10 VDC at 350 µA
Communication line
20.6 V peak-to-peak
maximum
Current
350 µA
Standby
500 µA
Activated
Wire size
12 to 18 AWG (0.75 to 2.5 mm²)
Compatible electrical boxes
North American 2-1/2 in. (64 mm)
deep single gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep box with single gang
mud ring
Special order surface mount
27193-10 - Cream enamel finish
boxes
27193-11 - Red enamel finish
Replacement glass rods
USA, P/N 270-GLR (pkg. 20 rods)
CAN, P/N 27165 (pkg. 12 rods)
Operating environment
Temperature
32 to 120°F (0 to 49°C)
Relative humidity
0 to 93% noncondensing at
90°F (32°C)
Storage temperature range
–4 to 140°F (–20 to 60°C)
Regulatory information
Environmental
UL: Indoor dry
class
North American
UL 38, CAN/ULC-S528
standards
Contact information
For contact information, see www.kidde-esfire.com.
2 / 2
firealarmresources.com
P/N 3101089-EN • REV 007 • ISS 21OCT20