WIRING CONNECTION
10

Connecting cables between indoor unit and outdoor unit

Outdoor
unit
3
2
1
CAUTION
!
The power cable connected to the outdoor unit should be complied with IEC 60245 or HD 22.4 S4
(This equipment shall be provided with a cable set complying with the national regulation.
10±3 mm
For the 1-Phase
10±3 mm
For the 3-Phase
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be provided with a cable set complying with the national
regulation.)
10±3 mm
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm
If the supply cable is damaged, it must be replaced by a special cable or assembly availible
from the manufacturer of its service agent.
Indoor
unit
3
2
1
Model
APUQ55GT3E0
APUQ55GT3M0
APUW55GT3E0
APUW55GT3M0
APUQ55GT3A0
APUW50GT3E0
APUQ55LT3E0
APUQ55LT3M0
APUW55LT3E0
APUW55LT3M0
APUQ50LT3E0
APUW50LT3E0
When the connection line between the indoor unit and out-
dooor unit is over 40 m, connect the telecommunication
line and power line separately.
2
2
Phase(Ø)
Area(mm
) Cable Type
1
6.0
3
2.5
H07RN-F
H07RN-F