SET UP MENU

Before setting up the control for use, the amount of ventilation air being delivered (CFM) by
the installed ventilation system must be measured.
1
2
  Hold for 5 seconds,
then release .
Throughout the Set Up Menu, the
and
is used enter the value and move on to the next Set Up Menu item .
NOTICE
buttons are used to change values, the Select button
14
Menu Item
Values
HP
HP or HC
HC
CODE
# BEDROOMS
HIGH
1 – 10
2
COMFORT
HOUSE (FT
)
LOW
500 – 7500 ft2
30 – 250 CFM
MEAS
REQ'D CONT
CFM
FAN
CODE NO.OF BEDROOMS
HIGH
HP
°F
OFF, 85°F – 105°F
COMFORT HOUSE (FT
2
)
LOW
HP
°F
OFF, -10°F – 40°F
On, "bLnd", OFF
MEAS REQ'D CONT CFM
FAN
CODE # BEDROOMS
HIGH
OFF, 60°F to 5°F
HP
°F
less than Vent .
High Temp . Limit
MEAS REQ'D CONT CFM
FAN
Description
HP if wiring to a heat pump .
HC if wiring to furnace and AC .
Number of bedrooms – used to calculate required
continuous ventilation rate .
Square footage – used to calculate required continuous
ventilation rate .
Measured outdoor airflow delivered during ventilation .
Ventilation high temperature limit. Ventilation is limited
when the outdoor temperature exceeds the setting . Turn
OFF if no high limit is desired .
Ventilation low temperature limit. Ventilation is limited
when the outdoor temperature falls below the setting .
Turn OFF if no low limit is desired .
ON HVAC fan turns on whenever ventilation occurs .
bLnd (blend) HVAC fan turns on with ventilation only
when the outdoor temperature is outside a set range .
OFF HVAC fan is not turned on with ventilation .
Only available when bLnd is selected . When the outdoor
temperature is above the setting, the HVAC fan will be
turned on to mix (blend) outdoor air with indoor air for
tempering .