Fixing the installation plate

You can select the direction of the drain hose depending on where you want to
install the indoor unit. Therefore before xing the installation plate to a wall or a
window frame, you must determine the position of the 65mm hole through which
the cable, pipe and hose pass to connect the indoor unit to the outdoor unit.
When facing the wall, the pipe and cable can be connected from the:
Right (A)
-
-
Left (B)
-
Underside_right (C)
-
Rear_right or left (D)
1
Determine the position of the pipe and drain hose hole as seen in the picture
and drill the hole with an inner diameter of 65mm so that it slants slightly
downwards.
CAUTION Make sure to drill only one hole after choosing the direction of
the pipe.
2
Fix the indoor unit.
If y
x the indoor unit on a wall
(1) Fix the installation plate to the wall giving attention to the weight of the
indoor unit.
Note
If you mount the plate to a concrete wall using plastic
anchors, make sure that gaps between the wall and the plate,
created by projected anchor, is less than 20 mm.
Plastic Anchor
<20 mm
If y
x the indoor unit on a window frame
(1) Determine the positions of the wooden uprights to be attached to the
window frame.
(2) Attach the wooden uprights to the window frame giving attention to
the weight of the indoor unit.
(3) Attach the installation plate to the wooden upright using tapping
screws.
• Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not
strong enough to withstand the product weight, the unit could fall and cause injury.

Purging the Indoor Unit

Unscrew the caps at the end of each pipe.
Result:
All inert gas exhausts from the indoor unit.
• To prevent dirt or foreign substances from getting into the pipes during
installation, do NOT remove the caps completely until you are ready to
connect the pipes.
• The remaining air in the Refrigeration cycle, which contains moisture,
may cause malfunction on the compressor.
• Always contact the service center or a professional installation agency
for product installation.
28
Wall
Direction of pipe
A
D
D
C
(Unit : mm)
**09U**Q
Pipe hole
(Ø65mm)
75
55
**09U*P ,**12** ,**18U**Q
(Unit : mm)
Pipe hole
(Ø65mm)
120
68
**18U*P , **24 **
(Unit : mm)
Pipe hole
(Ø65mm)
170
85
• Fix the installation plate without inclining to one side.
Pipes
Unscrew the caps
B