Installation Procedure
CAUTION
• When the float switch is not detected due to
insufficient water on the drain pan, the drain
pump will not work.
• If the power supply is directly connected to the
L and N terminals, communication error message
might appear.
• After completing the drainage check, turn the
unit off and disconnect the power supply.
• Reassemble the control box cover.
c Check whether the drain pump works correctly.
d Check whether the drainage is performing
correctly at the end of the drain pipe.
e Check for leakage at the drain pipe and drain pipe
connection part.
f When leakage occurs, check whether the indoor
unit is level and check the drain hose connection
part, drainpipe connection part and drain pump
connection.
g When the drainage check is completed and the
condensed water remains on the drain pan,
remove the water.
Step 12 Optional: For the installation
of the circular panel
Making a circular opening on the ceiling
Use a paper compass printed on the indoor unit package.
(attached inside to the upper part)
1 Use a bolt or a pin to fix pivot point of the paper
compass on center of the ceiling. (in the middle of
location for installation)
16
English
CAC_R32_호주향 360 IM_EN_DB68-08492A-01.indb 16
2 Put a pencil at the opposite side of the pivot point
fixed in place.
3 Rotate the paper compass on its pivot point to draw a
line on the ceiling.
4 Rotate the paper compass diametrically to draw a
circle on the ceiling.
For the painting of the panel
• Make sure to only apply paints and varnishes for
resins (ABS, HIPS) or paint thinners.
• If you apply lacquers for general use on the panel, it
may lead to discoloration or erosion on the surface of
the panel.