Step 8 — Install Electrical Connections
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground
screw in the control compartment, or conduit approved for
electrical ground when installed in accordance with NFPA
70 (NEC) (latest edition) (in Canada, Canadian Electrical
Code CSA C22.1) and local electrical codes.
CAUTION
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit being installed.
1. Make all electrical connections in accordance with
NFPA 70 (NEC) (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field- -supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high- -voltage power to unit is within
operating voltage range indicated on unit rating plate. On
3- -phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of
improper voltage and/or phase imbalance.
4. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit,
etc.
HIGH- - VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a
field- -supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field- -supplied disconnect may be mounted on the unit over
the high- -voltage inlet hole when the standard power and
low- -voltage entry points are used. See Fig. 2 and 3 for acceptable
location.
See unit wiring label (Fig. 15 and 17) and Fig. 10 for reference
when making high voltage connections. Proceed as follows to
complete the high- -voltage connections to the unit.
Single phase units:
1. Run the high- -voltage (L1, L2) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire from connection 11 of the
compressor contactor.
51801210406
CONTROL BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
Fig. 10 - - High- - and Control- -Voltage Connections
5. Connect field wire L2 to yellow wire from connection 23 of
the compressor contactor.
Three- -phase units:
1. Run the high- -voltage (L1, L2, L3) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire from connection 11 of the
compressor contactor.
5. Connect field wire L3 to yellow wire from connection 13 of
the compressor contactor.
6. Connect field wire L2 to blue wire from compressor.
SPECIAL PROCEDURES FOR 208- - V OPERATION
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main
power to system and install lockout tag. With disconnect
switch open, move black wire from transformer (3/16
in.)(4.8 mm) terminal marked 230 to terminal marked 208.
This retaps transformer to primary voltage of 208 vac.

CONTROL VOLTAGE CONNECTIONS

NOTE: Do not use any type of power- -stealing thermostat. Unit
control problems may result.
Use no. 18 American Wire Gage (AWG) color- -coded, insulated
(35C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft (30.5 m) from the unit (as measured along the
control voltage wires), use no. 16 AWG color- -coded, insulated
(35 C minimum) wires.

STANDARD CONNECTION

Locate the nine low voltage thermostat leads in 24 volt splice box.
See Fig. 10 for connection diagram. Run the low- -voltage leads
from the thermostat, through the control wiring inlet hole grommet
(Fig. 2 and 3), and into the low- -voltage splice box. Provide a drip
loop before running wires through panel. Secure and strain relief
all wires so that they do not interfere with operation of unit.
Specifications are subject to change without notice.
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
3-PHASE SHOWN
1-PHASE USES
TWO POWER
EQUIP GR
LEADS
FIELD-SUPPLIED
FUSED DISCONNECT
WHT(W2)
W2
VIO (W3)
W3
YEL(Y1)
GRN(G)
RED(R)
BRN(C)
ORN(O)
BLU (DH)
DH
PINK (Y2)
SPLICE BOX
WARNING
!
POWER
SUPPLY
Y1
G
THERMOSTAT
R
(TYPICAL )
C
O
DH WIRE IS ON
208/230 VAC MODELS
ONLY.
Y2
A13176
9