X K15, K16: Changing defrost option table
X
Switch
K15
ON
ON
OFF
OFF
❋ ❋ Defrost mode will start when the temperature difference between outdoor and outdoor heat exchanger has become
more than certain standard .
❋ ❋ Factory default status is MID . When the function changes to LOW with option control, defrost entering temperature
decreases . When defrost entering temperature decreases, the operation hour will be long but this means that the
operation hour with the reduced heating capacity increases . This option is used at places where humidity is high and the
defrost mode enters too frequently .
❋ ❋ Maintaining factory default status is recommended .
Setting the option
1) Press and hold K2 to enter the option setting . (Only available when the operation is stopped)
- If you enter the option setting, display will show the following . (If you have set the 'Emergency operation for compressor
malfunction' , 1 or 2 will be displayed on Seg 4 . )
- Seg 1 and Seg 2 will display the number for selected option .
- Seg 3 and Seg 4 will display the number for set value of the selected option .
2) If you have entered option setting, you can shortly press the K1 switch to adjust the value of the Seg 1, Seg 2 and select
the desired option . (Refer to pages 87~89 for the Seg number of the function for each option)
Example)
3) If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change
the function for the selected option . (Refer to pages 87~89 for the Seg number of the function for each option)
Example)
K16
ON
OFF
ON
OFF
Function
MID
MID
LOW1
LOW2