Capacity(kBtu)
Model
Ceiling
(AM✴✴✴FNCDC✴/AA,
AM✴✴✴JNCDC✴/AA)
V-AHU
(AM✴✴✴JNZDC✴/AA)
Ex) When the indoor unit AM023FN1DCH/AA and AM052FNDNCH/AA are combinated
Additional refrigerant charging = 250g + 450g = 700g
3) The total amount of additional refrigerant charging = the amount of refrigerant charging for pipe + the amount of
refrigerant for each indoor unit .
Ex) The amount of additional refrigerant charging = 3600g + 700g = 4300g
Connecting the drain hose to the outdoor unit
When using the air conditioner in the heating mode, ice may accumulate . During de-icing (defrost operation), the
condensed water must be drained off safely . Consequently, you must install a drain hose on the outdoor unit,
following the instructions below .
X Leave space of more than 50mm (1 . 9 7 inch) between the bottom of the outdoor unit and the ground for installation of
X
the drain hose, as shown in figure .
X Insert the drain plug into the hole on the underside of the outdoor unit .
X
X Connect the drain hose to the drain plug .
X
X Ensure that the drained water runs off correctly and safely .
X
50mm (1 . 9 7 inch)
X Be sure to plug the rest of drain holes not connected with drain plugs using drain caps .
X
Drain cap
6
7.5
9
9.5
Drain plug
12
15
18
20
24
0 . 3 9
0 . 3 9
(0 . 8 6)
(0 . 8 6)
0 . 3 3
0 . 5
0 . 5
(0 . 7 3)
(1 . 1 0)
(1 . 1 0)
13mm
'B'mm
(0 . 5 1 inch)
[Unit: kg(lb)]
27
30
36
48
54
0 . 5 6
0 . 9 5
(1 . 2 3)
(2 . 0 9)
0 . 8 3
0 . 8 8
1 . 1 8
1 . 2 7
(1 . 8 3)
(1 . 9 4)
(2 . 6 0)
(2 . 8 0)
27