Weil-McLain ULTRA299-S4 Manual page 60

Gas-fired water boilers
Table of Contents

Advertisement

S
4
®
ERIES
Multiple boiler installations
®
Easy-Fit
piping installation
1. Main header and Easy-Fit
a. New system — See page 10 .
b. Replacing boilers in an existing system — Without reducing
size, connect system supply and return lines. Install tees or
®
crosses for Easy-Fit
ure 61 . Size manifolds to handle total connected boiler output
as shown.
2. Provide connections in main header for Easy-Fit® manifolds as
close as possible to the midpoint of multiple boilers.
a. Use tees for four or less boilers, as in Figure 60 .
b. Use either tees ( Figure 60 ) or crosses ( Figure 61 ) for fi ve or
more boilers.
3. Manifold placement:
a. To alternate spacing for supply and return lines to boilers,
reverse the short-end and long-end of the manifolds as shown
in Figure 60 and Figure 61 .
b. Return manifold must be on the return side of the main and
supply manifold must be on the supply side of the main. Draw-
ings in this manual show fl ow in system main from right to
left. For system fl owing left to right, reverse the locations of
the manifolds accordingly.
4. Connect from Easy-Fit® manifold branches to boiler supply and
return connections using copper or steel pipe, sized for the required
fl ow rate.
5. Provide a fl ow/check valve in the supply piping of each boiler as
shown in piping diagrams in this manual. Install an isolation valve
on the supply and return of each boiler as shown. Some local codes
may require the use of individual water level controls and limits
on each boiler when isolation valves are installed.
6. Install main system air eliminator and primary circulator in sup-
ply piping as shown in piping diagrams. Place expansion tank on
suction side of system circulator as shown.
7. Install system accessories as shown in drawings.
8. Piping recommendation drawings:
a. Figure 60 and Figure 61 show details of Easy-Fit
b. Figure 62, page 61 is a schematic piping drawing showing the
locations of typical boiler piping and system piping, including
limits and other devices often required by local codes.
c. Figure 63, page 62 and Figure 64, page 63 are three-dimensional
piping drawings of typical multiple boiler installation.
d. Figure 65, page 64 shows recommended piping when an isolat-
ing heat exchanger is needed.
9. If desired, other primary/secondary piping arrangements can be
used.
When using isolation valves on each boiler, some codes
may require providing a low water control and additional
limit for each boiler. Consult local codes to determine
if omission of the individual boiler isolation valves
may allow the use of a single water level control and
additional limit for the entire multiple boiler system.
. This will satisfy some code requirements for
low water cutoff protection.
60
-
GAS
FIRED WATER BOILER
®
Manifold pipe sizing.
manifolds as shown in Figure 60 or Fig-
®
— Boiler Manual
(continued)
manifolds.
Single-sided EZ-Fit Header connection
Double-sided EZ-Fit Header connection
Part number 550-100-400/0717

Advertisement

Table of Contents
loading

This manual is also suitable for:

4 seriesUltra230-s4

Table of Contents