Multiple Unit Installation - Mitsubishi Electric m-MOCU-G02-050 Installation Manual

Outdoor unit for it cooling application
Table of Contents

Advertisement

(3) When there are overhead obstacles
≥ 240 (9-1/2)
≥ 45°
≥ 50 (2)

7-2. Multiple unit installation

・When installing multiple units, make sure to take into consideration factors such as providing enough space for
people to pass through, ample space between blocks of units, and sufficient space for airflow. (The areas marked
with Ⓐ in the figures below must be left open.)
・In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1"
through "h3" in the figures) to L1, L2, and L3 as shown in the tables below.
・If there are walls in the front and rear of the block of units, up to three units can be installed consecutively side by
side, and a space of 1000 mm (39-3/8 in) or more must be left between each block of three units.
(1) Side-by-side installation
When the distances between the units (L4) need to
be small
L4
Unit height
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
300 (11-13/16) + h2
(2) Face-to-face installation
When there are walls in the front and rear of the
block of units
h1
Unit height
L1
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
100 (3-15/16) + h2
VG79D920H01
h2
500 (19-11/16)
h1
L2
L1
L2 (Rear)
L4 (Between)
30 (1-3/16)
h2
500 (19-11/16)
L2
L4
L4
L2 (Rear)
L4 (Between)
450 (17-3/4)
≥ 1000 (39-3/8)
Air outlet guide
(not supplied)
When the distance behind the block of units (L2) needs
to be small
L4
Unit height
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
100 (3-15/16) + h2
When there is a wall on either the right or left side of the
block of units
h3
Unit height
L3
Required minimum distance [mm (in)]
L3 (Right/Left)
L4 (Between)
15 (5/8) + h3
11
h2
500 (19-11/16)
h1
L2
L1
L2 (Rear)
L4 (Between)
100 (3-15/16)
L4
L4
450 (17-3/4)

Advertisement

Table of Contents
loading

Table of Contents