Fault (RDC2)
Fault (OnCuer
Plus)
PrimLoopOpn
Primary Loop
Warning
Open
PrimLoopSht
Primary Loop
Warning
Shorted
Spd Sens Flt
Speed Sensor
Shutdwn
Fault
Volts L1-L2 High
High Generator
Shutdwn
Voltage L1-L2
Volts L1-L2 Low
Low Generator
Shutdwn
Voltage L1-L2
Volts L2-L3 High
High Generator
Shutdwn
Voltage L2-L3
Volts L2-L3 Low
Low Generator
Shutdwn
Voltage L2-L3
Volts L3-L1 High
High Generator
Shutdwn
Voltage L3-L1
Volts L3-L1 Low
Low Generator
Shutdwn
Voltage L3-L1
Figure 2-5 Controller Fault Messages
28
Section 2 Generator Set Operation
Condition
Ignition coil 1 voltage is below normal or
there is an open circuit.
Ignition coil 1 voltage is abnormal.
Engine speed sensor has failed or engine
stalled. ECM is no longer reporting valid
speed.
Generator Voltage High. Output voltage
exceeds 120% of the system nominal voltage
for more than 2 seconds.
Generator Voltage Low. Output voltage falls
below 80% of the nominal system voltage for
more than 10 seconds.
Generator Voltage High. Output voltage
exceeds 120% of the system nominal voltage
for more than 2 seconds.
Generator Voltage Low. Output voltage falls
below 80% of the nominal system voltage for
more than 10 seconds.
Generator Voltage High. Output voltage
exceeds 120% of the system nominal voltage
for more than 2 seconds.
Generator Voltage Low. Output voltage falls
below 80% of the nominal system voltage for
more than 10 seconds.
Check
Check the battery voltage.
Contact an authorized
distributor/dealer for service and
provide the fault code.
Check the battery voltage.
Contact an authorized
distributor/dealer for service and
provide the fault code.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load by turning off
appliances and restart the generator
set.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load by turning off
appliances and restart the generator
set.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load by turning off
appliances and restart the generator
set.
Contact an authorized
distributor/dealer for service.