Rheem Raypak Hi Delta H Series Installation & Operating Instructions Manual page 38

Hide thumbs Also See for Raypak Hi Delta H Series:
Table of Contents

Advertisement

Certified
Model
Venting
No.
Material
992C
1262C
1532C
1802C
Category III
2002C
2072C
2342C
* Subtract 10 ft per elbow. Max. 3 elbows.
Maximum combustion air duct length terminated at 100 equivalent ft.
Use only the special gas vent pipes listed for use with
Category III gas burning heaters, such as the stainless
steel vents offered by Heat Fab Inc. (800-772-0739),
Protech System, Inc. (800-766-3473), Z-Flex (800-
654-5600)
or
American
(800-423-4270). Pipe joints must be positively sealed.
Follow the vent manufacturer's installation instructions
carefully.
Ducted Air - Horizontal Through-the-
Wall
Fig. 41: Ducted Air - Horizontal Through-the-Wall
Installation
These installations utilize the heater-mounted blower
to draw combustion air from outdoors and vent com-
bustion products to the outdoors.
The total length of the through-the-wall flue cannot
exceed 40 equivalent ft in length for the flue outlet.
Each elbow used is equal to 10 ft of straight pipe. This
Maximum
Vent
Equivalent
Size
Vent Length*
10"
70'
12"
Room Air
40'
Ducted
14"
Combustion
Air
16"
Table N: Category III Horizontal and Ducted Air
Metal
Products
38
Combustion Air
Air Inlet Max. Length*
Intake Pipe
Material
Galvanized Steel,
PVC,
ABS,
CPVC
will allow installation in one of the three following
arrangements:
40' of straight flue pipe
30' of straight flue pipe and one elbow
20' of straight flue pipe and two elbows.
The total length of air supply pipe cannot exceed the
distances listed in Table N. Each elbow used is equal
to 10 ft of straight pipe. This will allow installation in
any arrangement that does not exceed the lengths
shown in Table N.
The flue direct vent cap is not considered in the overall
length of the venting system.
Care must be taken during assembly that all joints are
sealed properly and are airtight.
The vent must be installed to prevent the potential ac-
cumulation of condensate in the vent pipes. It is
required that:
1. The vent must be installed with a slight downward
slope of not more than 1/4 inch per foot of hori-
zontal run to the vent terminal.
2. The vent must be insulated through the length of
the horizontal run.
For installations in extremely cold climate, it is re-
quired that:
1. The vent must be installed with a slight upward
slope of not more than 1/4 inch per foot of hori-
zontal run to the vent terminal. In this case, an
10"
12"
75'
100'
40'
75'