Preparation

Step 1.1 Choosing the installation
location
Overview of installation location requirements
125 mm
or more
You can select the direction of
Make at least one round to
reduce noise and vibration.
The actual units may look different from
Model
Minimum
✴✴09/12/18✴✴
✴✴24✴✴
Outdoor
Unit
Outer wall
Indoor
Unit
Cut insulation to have
rainwater drained
28 English
DB68-06031A-01_A5.indd 28
100 mm or more
125 mm
or more
Drain hose hole
draining (left or right).
Maximum pipe height: 15 m
Maximum pipe length: 30 m
the images depicted here.
(Unit : m)
Pipe length
Pipe height
Maximum
Maximum
3
15
7
3
20
8
Make a U-trap (A) on the
pipe (which is connected to
the indoor unit) at outer wall
CAUTION
and cut the bottom part of
the insulation (about 10 mm)
to prevent rainwater from
getting inside through the
insulation.
CAUTION
• Comply with the length and height limits described
in the figure above.
Minimum clearances for the outdoor unit
Wall
Minimum clearance in mm
600
Air flow direction
Top view
When installing 1 outdoor unit
150
600
300
Side view
(6 cases)
(Unit: mm)
2000
4/18/2017 8:59:36 AM