Massachusetts Requirements - Superior Fireplaces DRC6340TYN Installation And Operation Instruction Manual

Power-vent direct-vent gas fireplaces
Hide thumbs Also See for DRC6340TYN:
Table of Contents

Advertisement

INNOVATIVE HEARTH PRODUCTS • POWER VENT DV GAS FIREPLACES (DRC/DRT6340TYN AND DRC/DRT6345TYN) • INSTALLATION INSTRUCTIONS
Input (BTU/HR), Natural Gas
Model No.
40"
45"
Input (BTU/HR), Propane Gas*
40"
45" Traditional
45" Contemporary
Table 1
*if field converted to LP
Gas Pressure - All Models
Tables 2 and 3 show the appliance inlet and
manifold gas pressure requirements.
Inlet Gas Supply Pressure
Natural Gas
Minimum Maximum
Minimum
5.0" WC
10.5" WC
11.0" WC
(1.25 kPa)
(2.62 kPa)
(2.74 kPa)
Table 2
Manifold Gas Supply Pressure
Natural Gas
Low
High
1.6" WC
3.5" WC
6.3" WC
(.40 kPa)
(.87 kPa)
(1.57 kPa)
Table 3
Test gauge connections are provided on the front
of the gas control valve; identified IN for the inlet
and OUT for the manifold side (see Figure 1).
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
(From DFC Wire
Manifold (Out)
Test Port
Inlet (In) Test Port
Wire
(From DFC Wire
Harness)
Main Gas Inlet
3/8" NPT
Figure 1 - SIT Electronic Gas Valve
6
The appliance must be isolated from the gas
supply piping system by closing its equipment
Input (BTU/Hr)
shutoff valve during any pressure testing of
26,500 - 42,000
the gas supply piping system at test pres-
35,000 - 48,000
sures equal to or less than 1/2 psi (3.5 kPa).
Gas Valve Diagram
26,500 - 42,000
See Figure 1 for gas valve diagram.
35,000 - 48,000
__,000 - 40,000
PURGE CYCLE
This is a power vented fireplace that
requires household electrical power
to operate. It will not operate during
a power failure. When the fireplace
is turned off, the exhaust blower will
continue to operate for approximately
fifteen (15) seconds after shutdown
to expel the exhaust gases from the
Propane Gas
venting system.
Maximum
Orifice Sizes - Sea Level To High Altitude
13.0" WC
These appliances are tested and approved for
(3.23 kPa)
installation at elevations of 0 - 4500 ft (0 - 1370
m) above sea level, using the standard burner
orifice sizes (marked with an "*" in Table 4).
For elevations above 4500 ft, contact your gas
supplier or qualified service technician.
Propane Gas
Deration - At higher elevations, the amount
Low
High
of BTU fuel value delivered must be reduced
10.0" WC
by either:
(2.49 kPa)
• Using gas that has been derated by the gas
company.
• Changing the burner orifice to a smaller size
as regulated by the local Authorities Having
Jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition, or in Canada, the CAN/CGA-B149.1
code - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction, and
the (USA) National Fuel Gas Code NFPA 54 /
ANSI Z223.1 - latest edition,
or (Canada) CAN/CGA-B149.1 - latest edition.
Green Wire
Harness)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: Flame appearance will diminish 4%
per one thousand feet of altitude.
Model
Table 4
In Canada - CAN/CGA-2.17-M91 (R2009) (high
altitude):
THE CONVERSION SHALL BE CARRIED OUT
BY A MANUFACTURER'S AUTHORIZED REP-
RESENTATIVE, IN ACCORDANCE WITH THE
REQUIREMENTS OF THE MANUFACTURER,
PROVINCIAL OR TERRITORIAL AUTHORITIES
HAVING JURISDICTION AND IN ACCORDANCE
WITH THE REQUIREMENTS OF THE CAN/CGA-
B149.1 OR CAN/CGA-B149.2 INSTALLATION
CODES.
COMMONWEALTH OF MASSACHUSETTS
REQUIREMENTS
These appliances are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R. Sections 4.00 through 8.00.
• Installation and repair must be done by a
• The flexible gas line connector used shall
• The individual manual shut-off must be a
Massachusetts Horizontal Vent Requirements
Connect GTMS
In the Commonwealth of Massachusetts, hori-
Wire Harness
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
Pressure
• A hard wired carbon monoxide detector
Regulator
Tower
Yellow Ground Wire
• A metal or plastic identification plate must
(From DFC Wire
Harness)
Burner Orifice Size
Elevation 0 - 4500 ft (0 - 1370 m)
Natural Gas
Propane Gas
0.125" (1/8") *
0.082" (#45)
40"
H7924 •
0.136" (#29) *
0.086" (#44)
45"
H8141 •
0.125" (1/8") *
0.082" (#45)
40"
H7924 •
0.136" (#29) *
0.073" (#49)
45"
H7921 •
* Standard size installed at factory
• Part /Cat. Number
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
not exceed 36 inches (92 centimeters) in
length.
T-handle type valve.
with an alarm and battery back-up must be
installed on the floor level where the gas
fireplace is installed. The carbon monoxide
detector must comply with NFPA 720, be
ANSI/UL 2034 listed and be ISA certified..
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
feet above grade and be directly in line with
the horizontal termination. The sign must
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.
J8002 •
H2287 •
J8002 •
H8807 •