Onboard DACT

The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a cen-
tral station. Pressing 2 while viewing the Option Module Screen will cause the following screens
to be displayed:
1=PRIM PHONE
2=SCND PHONE
3=CENTRAL STATION
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Primary Phone
Press 1 while viewing Onboard DACT Screen to program the type of primary phone line being
connected to the DACT. The following screen will be displayed:
1=TOUCHTONE
2=ROTARY 67/33 (EURO)
3=ROTARY 60/40 (U.S.)
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33, or 3
to select Rotary dialing with a make/break ratio of 60/40.
Secondary Phone
Press 2 while viewing Onboard DACT Screen 1 to program the type of secondary phone line being
connected to the DACT. The following screen will be displayed:
1=TOUCHTONE
2=ROTARY 67/33 (EURO)
3=ROTARY 60/40 (U.S.)
ON BOARD DACT
TCH TNE
TCH TNE
Onboard DACT Screen 1
ON BOARD DACT
Onboard DACT Screen 2
PHONE LINE
Primary Phone Type Screen
PHONE LINE
Secondary Phone Type Screen
Programming
89