Programming
INPUT ZONE #
1=FREEZE SUPV.
NO
2=ACC MSG #
Edit Input Zone Screen #4
INPUT ZONE #
1=ADJECTIVE/NOUN
2=DESCRIPTION
*****************
Edit Input Zone Screen #5
66
ACC Message
Pressing 2 for ACC MSG # while viewing Edit Input Zone Screen #4 will cause the following
screens to be displayed:
1=NO MSG-ACTIVE
2=NO MSG-INACTIVE
3=MESSAGE 1
1=MESSAGE 2
2=MESSAGE 3
3=MESSAGE 4
1=MESSAGE 5
Using these screens, the programmer can assign an audio message to each input zone. The NO
MSG-ACTIVE option is the factory default selection which means that no message has been pro-
grammed for the input zone but its corresponding ACC-25/50ZST audio zone will turn on when
this input zone goes active (if an input zone with a programmed audio message goes active, the
message will also be played over this zone). The NO MSG-INACTIVE option will not turn on the
corresponding ACC-25/50ZST audio zone when this input goes active. If MESSAGE 1 through 5
is the programmed option, the selected message will play when the FACP is connected to an ACC-
25/50ZST Audio Panel via the ANN-BUS and the corresponding FACP input zone goes into alarm.
Adjective/Noun
The Adjective/Noun selection allows the programmer to enter specific descriptors about the detec-
tor currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #4 will cause
the following screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
ACC MSG NUMBER
ACC Message Screen #1
ACC MSG NUMBER
ACC Message Screen #2
ACC MSG NUMBER
ACC Message Screen #3
Adjective/Noun Screen
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012