Page 2
Battery Warnings • Connect only Tripp Lite battery packs to the battery connectors. Connect battery packs of the correct voltage and type. • Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the batteries in a fire.
Features The SMART3000RMOD2U UPS System features a hot-swappable power module. When the bracket holding the power module in place is removed (there is no manual bypass switch on the unit), the UPS automatically switches to “BYPASS” mode. This allows the power module to be removed for mainte- nance, repair or replacement without disrupting power to connected loads.
Serial and USB Ports: These serial (RS-232 DB9) and USB ports enable optional connection of the UPS to corresponding ports on a workstation or server. When the UPS System is connected to a computer via the included serial or USB cable, Tripp Lite’s PowerAlert Software can be used to monitor and control the UPS System.
Page 5
2-Post (Telecom) Mounting If you mount the SMART3000RMOD2U in a 2-post rack, it requires the addition of a Tripp Lite 2-Post Rackmount Installation Kit (Model: 2POSTRMKITWM, sold separately). Attach mounting ears...
Mounting ( continued ) Mounting (Tower) Mount the UPS System in a vertical or tower position using 2-9USTAND base stands (sold separately). The user must determine the fitness of hardware and procedures before mounting. WARNING! The UPS system is extremely heavy. Use caution when lifting and mounting. User must properly stabilize the UPS when lifting and mounting.
Quick Installation Plug the UPS into an outlet on a dedicated circuit. NOTE: After you plug the UPS into a live AC outlet, the UPS will automatically charge its batteries* and will supply power to its outlets unless the unit is turned OFF (see Step 3 below). Plug your equipment into the UPS.* * Your UPS is designed to support only electronic equipment.
The Battery Configuration Port automatically detects up to four external Tripp Lite battery packs and also estimates the remaining battery run time. Using the included RJ-45 cable , connect the Battery Configuration port to a user-supplied Tripp Lite external battery pack.
Basic Operation Indicator Lights (Front Panel) “ON” Button • To turn the UPS ON: the button after you hear a beep. If utility power is absent, you can “cold-start” the UPS (i.e.: turn it ON and supply power for a limited time from its batteries, if they’re fully charged) by pressing and holding the “ON”...
Page 10
Basic Operation ( continued ) Load Level/Battery Capacity Indicator Lights (Front Panel) ”Load/Battery” Bar Graph: The LED bars indicate the level of the output load and battery capacity. 100% Load/Battery Bar LED Load Bar graph: 81%-105% load (Yellow) Battery Bar Graph: 81%-100% battery capacity (Green) 80% Load/Battery Bar LED Load Bar graph: 61%-85% load (Green) Battery Bar Graph: 61%-80% battery capacity (Green)
Page 11
4 external Tripp Lite battery packs. Accessory Slot: Remove the small cover panel from this slot to install optional accessories (such as Tripp Lite’s Relay I/O Card) to remotely monitor and control your UPS. Refer to your accessory’s manual for installation instructions. Contact Tripp Lite Customer Support at (773) 869-1234 for more information, including a list of available SNMP, network management and connectivity products.
Power Module Replacement The SMART3000RMOD2U features a hot-swappable power module. There is no manual bypass switch on the unit. However, when the bracket holding the power module in place is removed (see Step #3 below), the UPS will automatically switch to “BYPASS” mode, allowing the power module to be removed for maintenance, repair or replace- ment without disrupting power to connected loads.
Battery Replacement Step 1: Remove front panel Step 2: Disconnect battery connectors Step 3: Remove the screws that secure the battery retention bracket in place. Step 4: Remove battery retention bracket Step 5: Remove/recycle battery Step 6: Replace the battery Step 7: Re-attach battery retention bracket Step 8: Replace screws to secure battery...
Page 14
If the problem continues, do not contact or return the UPS to the dealer. Instead, call Tripp Lite at (773) 869-1233. A service technician will ask for the UPS's model number, serial number and purchase date and will attempt to correct the problem over the phone.
Seller will repair or replace the product, in its sole discretion. Service under this Warranty can only be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA. Seller will pay return shipping charges. Call Tripp Lite Customer Service at (773) 869-1234 before sending any equipment back for repair.
Page 16
1111 W. 35th Street, Chicago, IL 60609 USA (773) 869-1234 • www.tripplite.com...