2
General venting

Polypropylene

This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 2D.
All terminations must comply with listed options in this
manual and be a single-wall vent offering.
For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.
When determining equivalent combustion air and vent length
for polypropylene single-wall piping:
1 foot of Duravent 4 inch single-wall pipe is equivalent
to 1.6 feet of piping
Flexible polypropylene
For use of flex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations (FIG. 2-8).
Figure 2-8 Near Boiler Flexible Polypropylene Venting
CAP
"A" DIM
CHIMNEY
3" RIGID 3" FLEX 4" FLEX
10 FT
20 FT
30 FT
B
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
Centrotherm 3"
A
"A" DIM
3" RIGID 3" FLEX 4" FLEX
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
*NOTES: 1) FLEX PIPE MAY ONLY BE RUN IN A VERTICAL ORIENTATION
2) ALL VENT LENGTHS REPRESENTED IN ABOVE CHARTS ARE
EQUIVALENT LENGTHS.
3) SECTION A IS EQUIVALENT FEET OF RIGID PIPE, WHICH MAY
INCLUDE 45 AND 90° ELBOWS. PLEASE SEE SIZING SECTION
FOR DETERMINING EQUIVALENT FEET.
Table 2D Polypropylene Vent Pipe and Fittings
Approved Polypropylene Vent Manufacturers
Make
Centrotherm Eco Systems
Duravent (M & G Group)
Table 2E Approved PolypropyleneTerminations
Model
Polypropylene
Adapter
125 -- 200
ISAAL0303
285 -- 500
ISAAL0404
* These parts are only needed if the sidewall termination assembly is used (see FIG. 3-4B on page 28).
(continued)
Duravent 3"
Duravent 4"
"B" DIM
"A" DIM
"B" DIM
4" RIGID 4" FLEX
5" FLEX
60 FT
90 FT
10 FT
30 FT
53 FT
80 FT
20 FT
27 FT
47 FT
70 FT
30 FT
23 FT
40 FT
60 FT
40 FT
20 FT
33 FT
50 FT
50 FT
17 FT
27 FT
40 FT
60 FT
13 FT
20 FT
30 FT
70 FT
10 FT
13 FT
20 FT
80 FT
7 FT
7 FT
10 FT
90 FT
3 FT
Centrotherm 4"
"B" DIM
"B" DIM
"A" DIM
4" RIGID 4" FLEX
45 FT
10 FT
33 FT
90 FT
40 FT
80 FT
20 FT
29 FT
30 FT
26 FT
35 FT
70 FT
40 FT
22 FT
30 FT
60 FT
50 FT
18 FT
25 FT
50 FT
20 FT
60 FT
15 FT
40 FT
15 FT
30 FT
70 FT
11 FT
80 FT
7 FT
10 FT
20 FT
90 FT
4 FT
5 FT
10 FT
Model
InnoFlue SW/Flex
PolyPro Single-Wall / PolyPro Flex
Centrotherm InnoFlue SW
Joint
Sidewall Retaining
Connector
Bracket*
IANS03
IATP0303
IANS04
IATP0404
NOTICE
NOTICE
⚠ WARNING
⚠ WARNING
NOTICE
90 FT
NOTICE
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
Figure 2-9 Near Water Heater Polypropylene Venting
20 FT
10 FT
IMG00840
MODELS 125 - 200
Standard
UL-1738/ULC-S636
ULC-S636
Sidewall Adapter*
ISTAGL0303
ISTAGL0404
Installation & Service Manual
The installer must use a specific vent starter
adapter at the flue collar connection. The
adapter is supplied by the vent manufacturer
to adapt to its vent system. See Table 2E for
approved vent adapters.
Discard CPVC
starter piece.
All vent connections MUST be secured by
the vent manufacturer's joint connector
(FIG. 2-9).
Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.
Use only the adapters and vent system
listed in Tables 2D and 2E.
mix vent systems of different types or
manufacturers. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
Installations must comply with applicable
national, state, and local codes.
Canadian installation, polypropylene vent
must be listed as a ULC-S636 approved
system.
Installation of a polypropylene vent system
should adhere to the vent manufacturer's
installation instructions supplied with the
vent system.
JOINT CONNECTOR REQUIRED
AT ALL COMPONENT CONNECTIONS
OF VENT SYSTEM
POLYPROPYLENE
ADAPTER
MODELS 285 - 500
Duravent Polypro
Polypropylene
Joint
Adapter
Connector
3PPS-ADL
3PPS-LB
4PPS-AD-M
4PPS-LB
DO NOT
For
JOINT CONNECTOR REQUIRED AT
ALL COMPONENT CONNECTIONS
OF VENT SYSTEM
POLYPROPYLENE
ADAPTER
DIR #2000586643
Sidewall Kit*
3PPS-HLK
4PPS-HLK
21

Advertisement

Table of Contents
loading

Table of Contents