5

System Set Up

5.1 FTC

5.1.1 DIP Switch Function
Located on the FTC printed circuit board are 6 sets of small
white switches known as DIP switches. The DIP switch number
is printed on the circuit board next to the relevant switches. The
word ON is printed on the circuit board and on the DIP switch
block itself. To move the switch you will need to use a pin or the
corner of a thin metal ruler or similar.
DIP switch settings are listed below in Table 5.1.1.
Only an authorised installer can change DIP switch setting under
one's own responsibility according to the installation condition.
Make sure to turn off heat pump unit power supplies before
changing the switch settings.
DIP switch
SW1 SW1-1 Boiler
SW1-2 Heat pump maximum outlet water temperature 55ºC
SW1-3 DHW tank
SW1-4 Immersion heater
SW1-5 Booster heater
SW1-6 Booster heater function
SW1-7
SW1-8 Wireless remote controller
SW2 SW2-1 Room thermostat1 input (IN1) logic change
SW2-2 Flow switch1 input (IN2) logic change
SW2-3 Booster heater capacity restriction
SW2-4
Automatic switch to backup heat source op-
SW2-5
eration (When compressor stops by error)
SW2-6 Mixing tank
SW2-7 2-zone temperature control
SW2-8
SW3 SW3-1 Room thermostat 2 input (IN6) logic change
SW3-2 Flow switch 2,3 input (IN3,7) logic change
SW3-3
SW3-4 Electric energy meter
SW3-5
SW3-6 2-zone valve ON/OFF control
SW3-7
SW3-8 Heat meter
SW4 SW4-1
SW4-2
SW4-3
SW4-4 Water circuit only operation (during installation work) *2 Inactive
SW4-5 Emergency mode (Heater only operation)
SW4-6 Emergency mode (Boiler operation)
SW5 SW5-1
SW5-2 Advanced auto adaptation
SW5-3
SW5-4
SW5-5
Capacity code
SW5-6
SW5-7
SW5-8
SW6 SW6-1
SW6-2
SW6-3 Pressure sensor
SW6-4 Analog output signal (0-10V)
SW6-5 Model select
Note:
*1. External output (OUT11) will be available. For safety reasons, this function is not available for certain errors. (In
that case, system operation must be stopped and only the water circulation pump keeps running.)
*2. Space heating and DHW can be operated only in water circuit, like an electric boiler. (Refer to "5.1.5 Water circuit
only operation". )
*3. If emergency mode is no longer required, return the switch to OFF position.
*4. Active only when SW3-6 is set to OFF.
Function
WITHOUT Boiler
WITHOUT DHW tank
WITHOUT Immersion heater
WITHOUT Booster heater
For heating only
WITHOUT Wireless remote controller WITH Wireless remote controller
Zone1 operation stop at thermostat short Zone1 operation stop at thermostat open OFF
Failure detection at short
Inactive
Inactive
WITHOUT Mixing tank
Inactive
Zone2 operation stop at thermostat short Zone2 operation stop at thermostat open OFF
Failure detection at short
WITHOUT Electric energy meter WITH Electric energy meter
Inactive
WITHOUT Heat meter
Normal
Normal
Inactive
Inactive
Inactive
Air to Water
<Table 5.1.1>
OFF
WITH Boiler
60ºC
WITH DHW tank
WITH Immersion heater
WITH Booster heater
For heating and DHW
Failure detection at open
Active
Active *1
WITH Mixing tank
Active *4
Failure detection at open
Active
WITH Heat meter
Active
Emergency mode (Heater only operation) OFF *3
Emergency mode (Boiler operation) OFF *3
Active
Active
Active
Water to Water
SW5
SW4
SW3
SW2
SW1
SW6
<Figure 5.1.1>
Default
ON
settings
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
ON