Wiring Of The Control Circuit - Mitsubishi Electric FR-CV-7.5K Instruction Manual

Transistorized inverter
Table of Contents

Advertisement

Power
Regeneration
Terminal Name
Common
Converter Model
FR-CV-7.5K
FR-CV-11K
FR-CV-15K
FR-CV-22K
FR-CV-30K
FR-CV-37K
FR-CV-55K
R/L11, S/L21,
FR-CV-H7.5K
FR-CV-H11K
FR-CV-H15K
FR-CV-H22K
FR-CV-H30K
FR-CV-H37K
FR-CV-H55K
Note: 1. Wire the cables so that the phase sequence of the wiring in 4) is always identical to those of the wiring in
1) and 2).
Connection in wrong phase sequence will damage the power regeneration common converter.
2. To prevent a malfunction due to noise, run the cables away from the main circuit wiring.
3. Running the inverter without connecting terminals R/L11, S/L21 and T/MC1 to the power supply will
damage the power regeneration common converter.
5)
Connection of power supply and inverter
When the model used is the one whose control power is input from R1 and S1, control circuit power must be
input to R1 and S1 of the inverter. At this time, remove the jumpers across R-R1, S-S1.
2
Cable size: 0.75mm
to 2mm
Dedicated
stand-alone reactor (FR-CVL)
R/L11
S/L21
T/L31
Note: 1. Never connect a power supply to the inverter terminals R, S, T. Accidental connection will damage the
inverter and power regeneration common converter.
2. For the FR-A700, F700, A500, F500 or V500 series, disconnect the jumpers across terminals R-R1, S-
S1 and connect the control power supply to terminals R1, S1. For the FR-E700, D700, E500, S500,
C500 or F500J series, there are no terminals R1, S1 and you need not make the above connection.
2.2.3

Wiring of the control circuit

(1) Wiring instructions
1)
The terminals SD, SE are common to the I/O signals and are isolated from each other. Must not be earthed
(grounded).
2)
Shielded or twisted cables must be used for connection to the control circuit terminals, and also run away from
the main and power circuits (including the 200V relay sequence circuit).
3)
The input signals to the control circuit are micro currents. When contacts are required, use two or more parallel
micro signal contacts or a twin contact to prevent a contact fault.
4)
It is recommended to use the cables of 0.3mm
terminals.
Terminal
Screw Size
M4
M4
M4
M4
M4
M4
M4
T/MC1
M4
M4
M4
M4
M4
M4
M4
2
FR-CV
R2/L12
R2/L1
S2/L22
S2/L2
T2/L32
T2/L3
R/L11
S/L21
T/MC1
Tightening
Crimping
Torque N•m
Terminals
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
1.5
1.25-4
5)
P/L+
N/L-
2
2
to 0.75mm
gauge for connection to the control circuit
21
Wiring
Cables
2
AWG
mm
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
1.25
16
FR-A720
R/L1
S/L2
(Note1)
T/L3
R1/L11
(Note2)
S1/L21
P/
+
N/-
2