33303 LOCALLY PROCURED PARTS

3330333 AIR DISCHARGE DUCT
PRECAUTION
All the components/parts such as the duct, frame, and screws are to be locally procured.
Do not install the duct where seasonal wind blow directly against to the discharge port.
Install so that the static pressure of the air flow path
Note that installation of the duct increases the height of the cabinet.
If installation space may narrow, like as consecutive unit layout, be sure to fix the duct to the
unit before placing the unit.
When the duct is installed, the noise may become louder.
DUCT LAYOUT EXAMPLE
Model
AJ  A72LALH
AJ  A90LALH
AJ  108LALH
AJ  126LALH
AJ  144LALH
Make the height A of the duct opening section 500mm or greater.
Make the height B of the duct, excluding the flange 500mm or greater.
Make the width (dimension C) of the duct within the range of the table shown above.
Provide a Chamfer or round the corner at the air flow path.
Design the duct weight with 100kg or less as the standard.
Design the duct so that maintenance of the motor is possible.
When the length of the duct is long, provide support material at suitable intervals.
500
Dimension C
(Minimum)
(Maximum)
862
1172
Caution
- (03 - 49) -
, including the duct is 80Pa or less.
Chamfer or a round the corner
500
114
1576
928
1238
(Unit : mm)