ELECTRIC CHARACTERISTICS

SPACE SAVING COMBINATION
Rated Value
Power Supply
HP
Model name
Hz
8HP
AJ  A72LALH
50
10HP
AJ  A90LALH
50
12HP
AJ  108LALH
50
14HP
AJ  126LALH
50
16HP
AJ  144LALH
50
Select the breaker based on MCA of the table above.
Select the wire diameter based on the larger value of MCA or TOCA of the table above and select
a wire diameter which withstands the breaker capacity.
*1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with local rules.
*2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer,
select the wiring size of larger diameter.
RLA : Rated Load Amp of compressor under the standard condition.
MCA : Min Circuit Amp = Max Operating Current (Full Load)
MSC : Max Starting Current
TOCA : Total Value of Each Over Current Set
MFA : Main Fuse (Circuit Breaker) Current
Full Load Characteristics
Voltage
MCA
TOCA
MSC
(V)
(A)
(A)]
(A)
400
24.0
28.0
19.2
400
24.0
28.0
19.2
400
39.1
44.0
91.8
400
39.1
44.0
91.8
400
39.1
44.0
91.8
- (03 - 45) -
Electric Characteristics
Wiring Specifications *1
Limied
Power
Earth
MFA
Wiring
Cable
Cable
(A)
Length
2
2
(mm
)
(mm
)
(m) *2
30
4
4
30
30
4
4
30
50
10
6
42
50
10
6
42
50
10
6
42
Outdoor Fan
Compresser
Morter
Output
FLA
RLA
(kW)
(A)
(A)
10.2
0.6
3.2
10.2
0.6
3.2
10.2+10.0
0.6
3.2
10.2+10.0
0.6
3.2
10.2+10.0
0.6
3.2