6.3 Wire Routing
(1) Remove the screws and the cover.
(2) Pass the power supply wiring through the opening in the conduit panel.
(3) Fasten the conduit connection to the conduit panel using the lock nut.
(4) Connect the power supply wiring to the terminal.
(5) Secure the power supply wiring with the clamp.
(6) After completing the wiring, seal the wire opening with the sealing material.
(7) Reinstall cover after completing the work.
6.4 Electrical Installation
WARNING
● Use an ELB (Electric Leakage Breaker). If not used, it may cause an electric shock or a fire.
● Do not operate the system until all the check points have been cleared.
(A) Ensure the insulation resistance is more than 2MΩ, by measuring the resistance between
ground and the terminal of the electrical parts. If not, do not operate the system until the electrical leakage
is found and repaired.
(B) Check to ensure that the stop valves of the outdoor unit are fully opened and then start the system
Note:
(1) Follow national and local codes and regulations when selecting sizing field wiring, and all the above are the
minimum wire sizes.
(2) Use copper supply wires.
(3) When the transmission cable length exceeds 49 ft. (15m) , a larger wire size should be selected.
(4) Install main disconnect and ELB for each system separately. Select the high response type ELB that is acted within
0.1second.
1.When connecting the terminal block using stranded wire, make
sure to use the round crimp-style terminal for connection to the
power supply terminal block. Place the round crimp-style
terminals on the wires up to the covered part and secure in place.
2. When connecting the terminal block using a single core wire, be

7. Trial Run

Please perform trial run according to outdoor unit installation manual.
Cover
Conduit panel
Model Capacity(Btu/h)
9K~36K
<Attentions when Connecting the power supply wiring>
sure to perform curing.
Installation and Maintenance
Installation and Maintenance
Transmission
Cable Size
4×16AWG
covered part
Round crimp-style terminal
17
Power supply
wiring
Lock nut
Conduit
connector
Stranded wire
Terminal
Single core wire
.